Product Model

140DDI85300C

In Stock
Last updated: 2025/5/1
schneider 140DDI85300C

Selling Points

  • 1Designed for harsh environments with a conformal coating for enhanced protection.
  • 2Operates on a supply voltage of 10-60Vdc, ensuring versatility in various applications.
  • 3Backplane or rack mounting capabilities for secure and efficient installation.
  • 4Compatible with Unity Pro software in multiple programming languages (FBD, LD, SFC, IL, ST).
  • 5Specific power consumption formula of (0.25 x number of points on) + 1 W, minimizing energy usage.
Product Details
140DDI85300C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete input modules
Discrete input number
32
Group of channels
4
Logic input
Positive (sink)
input voltage limits
10...60 V
Input voltage
12 V 5…10 mA DC<br />24 V 6…30 mA DC<br />48 V 2…15 mA DC<br />60 V 1…5 mA DC
Voltage state 1 guaranteed
9...12 V 12 V +/- 5 %<br />11...24 V 24 V - 15...20 %<br />34...48 V 48 V - 15...20 %<br />45...60 V 60 V - 15...20 %
Voltage state 0 guaranteed
0...1.8 V 12 V +/- 5 %<br />0...10 V 48 V - 15...20 %<br />0...12.5 V 60 V - 15...20 %<br />0...5 V 24 V - 15...20 %
Absolute maximum voltage
75 V
Addressing requirement
2 input words
Response Time
4 ms from state 0 to state 1<br />4 ms from state 1 to state 0
Switching frequency
<= 100 Hz
Isolation between group and bus
2500 Vrms DC for 1 minute
Isolation between group
700 Vrms DC for 1 minute
Power dissipation
1 W + (0.25 x number of points on)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for input status 32 LEDs (green)
Bus current requirement
300 mA
Module format
Standard
Net Weight
0.650 lb(US) (0.295 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508<br />EN/IEC 61131-2
Product Certifications
CSA<br />CE<br />ATEX<br />Merchant Navy<br />IEC-Ex<br />UL<br />EAC<br />RCM<br />hazardous location class 1, division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice