Product Model
140DDM39000

Selling Points
- 1Versatile Industrial Automation Component: Manage both input and output signals with exceptional reliability.
- 2Modicon Quantum Integration: Seamlessly integrates into Schneider Electric’s Modicon Quantum system for precise control.
- 324 Discrete I/O Points: 16 inputs and 8 outputs, organized into manageable groups for efficient signal processing.
- 4Robust Protection Features: Includes multiple layers of protection against electrical disturbances, such as transient voltage suppression and resistor-limited input protection.
- 5High Load Flexibility: Each output point handles up to 0.5 A, with each group supporting up to 2 A and the module up to 4 A.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Mixed discrete I/O module |
Discrete I/O number | 24 | Discrete input number | 16 2 groups of 8 |
Discrete input logic | Sink | Addressing requirement | 1 input word<br />0.5 output word |
Network frequency limits | 47…63 Hz | Discrete input voltage | 24 V DC |
input voltage limits | 30 V<br /><= 1 V during one cycle<br />56 V during 1.3 ms<br /><= 1 V during 10 s | Voltage state 0 guaranteed | -3...5 V |
Voltage state 1 guaranteed | 15...30 V | Current state 0 guaranteed | <= 0.5 mA |
Current state 1 guaranteed | >= 2 mA | Input impedance | 2500 Ohm |
Discrete output number | 8 2 groups of 4 | Discrete output type | Solid state |
Discrete output logic | Sink | Discrete output voltage | 24 V |
Output voltage limits | 19.2...30 V DC typical<br />56 V DC during 1.3 ms | Maximum load current | <= 0.5 A per point<br /><= 2 A per group<br /><= 4 A per module |
Maximum voltage drop | <0.4 V 0.5 A | Absolute maximum output | 5 A during 500 µs per point |
Maximum load inductance | 500 mH 4 Hz | Maximum load capacitance | 50 µF |
Maximum leakage current | 0.4 mA 30 V DC | Response time on output | <= 1 ms at state 0 to state 1<br /><= 1 ms at state 1 to state 0 |
Protection Type | On output by transient voltage suppression<br />On input by resistor limited<br />Internal output protection by 5 A fuse per group | Associated fuse rating | 5 A per group |
Isolation between group | 500 Vrms for 1 minute | Isolation between group and bus | 1780 Vrms for 1 minute |
Fault indication | Blown fuse on output<br />Loss of field power on output | Power dissipation | 1.75 W + (0.36 x input point on) + (1.1 total output load current) |
Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for no voltage in output and input (F) 1 LED (red)<br /> for output is turned on 2 LEDs (green)<br /> for fault detected on the input point 2 LEDs (red)<br /> for fault detected on the output point 2 LEDs (red) | marking | CE |
Bus current requirement | 330 mA | Net Weight | 0.7 lb(US) (0.3 kg) |
Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |
Standards | CSA C22.2 No 142<br />UL 508<br />FM Class 1 Division 2 | Product Certifications | cUL |
Specifications may be subject to change without notice