schneider 140DDM39000

Selling Points

  • 1Versatile Industrial Automation Component: Manage both input and output signals with exceptional reliability.
  • 2Modicon Quantum Integration: Seamlessly integrates into Schneider Electric’s Modicon Quantum system for precise control.
  • 324 Discrete I/O Points: 16 inputs and 8 outputs, organized into manageable groups for efficient signal processing.
  • 4Robust Protection Features: Includes multiple layers of protection against electrical disturbances, such as transient voltage suppression and resistor-limited input protection.
  • 5High Load Flexibility: Each output point handles up to 0.5 A, with each group supporting up to 2 A and the module up to 4 A.
Product Details
140DDM39000
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Mixed discrete I/O module
Discrete I/O number
24
Discrete input number
16 2 groups of 8
Discrete input logic
Sink
Addressing requirement
1 input word<br />0.5 output word
Network frequency limits
47…63 Hz
Discrete input voltage
24 V DC
input voltage limits
30 V<br /><= 1 V during one cycle<br />56 V during 1.3 ms<br /><= 1 V during 10 s
Voltage state 0 guaranteed
-3...5 V
Voltage state 1 guaranteed
15...30 V
Current state 0 guaranteed
<= 0.5 mA
Current state 1 guaranteed
>= 2 mA
Input impedance
2500 Ohm
Discrete output number
8 2 groups of 4
Discrete output type
Solid state
Discrete output logic
Sink
Discrete output voltage
24 V
Output voltage limits
19.2...30 V DC typical<br />56 V DC during 1.3 ms
Maximum load current
<= 0.5 A per point<br /><= 2 A per group<br /><= 4 A per module
Maximum voltage drop
<0.4 V 0.5 A
Absolute maximum output
5 A during 500 µs per point
Maximum load inductance
500 mH 4 Hz
Maximum load capacitance
50 µF
Maximum leakage current
0.4 mA 30 V DC
Response time on output
<= 1 ms at state 0 to state 1<br /><= 1 ms at state 1 to state 0
Protection Type
On output by transient voltage suppression<br />On input by resistor limited<br />Internal output protection by 5 A fuse per group
Associated fuse rating
5 A per group
Isolation between group
500 Vrms for 1 minute
Isolation between group and bus
1780 Vrms for 1 minute
Fault indication
Blown fuse on output<br />Loss of field power on output
Power dissipation
1.75 W + (0.36 x input point on) + (1.1 total output load current)
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for no voltage in output and input (F) 1 LED (red)<br /> for output is turned on 2 LEDs (green)<br /> for fault detected on the input point 2 LEDs (red)<br /> for fault detected on the output point 2 LEDs (red)
marking
CE
Bus current requirement
330 mA
Net Weight
0.7 lb(US) (0.3 kg)
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)
Standards
CSA C22.2 No 142<br />UL 508<br />FM Class 1 Division 2
Product Certifications
cUL

Specifications may be subject to change without notice