Product Model
140SDO95300S

Selling Points
- 116 discrete outputs for versatile control
- 2Operating voltage range of 19.2 to 30VDC
- 3Positive logic (source) addressing requirement
- 4Surge current of 2A for 10ms for robust performance
- 5CE, TÜV Rheinland (SIL2), CSA, and UL certified for safety
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Quantum automation platform | Product or Component Type | Safety dc discrete output module |
Discrete output number | 16 | Group of channels | 1 |
Discrete output logic | Positive logic (source) | Addressing requirement | 4 output words<br />7 input words |
Discrete output voltage | 19.2...30 V DC | Absolute maximum output | 34 V |
Maximum voltage drop | <0.3 V 0.5 A | Sensor power supply | 19.2…30 V |
Maximum load current | <= 0.65 A each point<br /><= 10.04 A each group | Surge current | 2 A 10 ms |
Response Time | <= 20 ms at state 0 to state 1<br /><= 20 ms at state 1 to state 0 | Maximum leakage current | 0.5 mA 30 V |
Protection Type | With | Load inductance | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))<br />0.5 8 Hz |
Fault indication | Channel fault<br />Overload<br />Power supply fault<br />System fault | Associated fuse rating | 10 A |
Isolation between channels and bus | 1500 Vrms for 1 minute | Isolation between group and bus | 1500 Vrms for 1 minute |
Power dissipation | 1.9 W + 0.65 I² | marking | CE |
Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for output status 16 LEDs (green)<br /> for system failure, diagnostic of internal channel fault 16 LEDs (red) | Bus current requirement | 350 mA |
Product Certifications | TÜV Rheinland (SIL2)<br />CSA<br />CSA HazLoc<br />UL<br />C-tick |
Specifications may be subject to change without notice