Selling Points

  • 1Efficient Motor Control: The ATS22C41S6 soft starter provides smooth starting and stopping of 3-phase asynchronous motors, minimizing mechanical stresses and extending service life.
  • 2High Power Rating: Supports motor power ratings from 110 kW to 250 kW, making it suitable for a wide range of industrial applications.
  • 3Compact Design: Slim form factor allows for versatile mounting in various machine frames, optimizing enclosure size and reducing heat dissipation.
  • 4Integrated Bypass: Reduces noise and decreases heat dissipation with an integrated bypass feature, enhancing overall system reliability.
  • 5Easy Configuration: Compatible with SoMove software for easy configuration and setting transfer via Bluetooth or cable, ensuring quick installation of spares.
Product Details
ATS22C41S6
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altistart 22
Product or Component Type
Soft starter
Product destination
Asynchronous motors
Product Specific Application
Pumps and fans
Component name
ATS22
Phase
3 phase
[Us] rated supply voltage
230...600 V - 15...10 %
Motor power kW
110 kW 230 V<br />220 kW 400 V<br />220 kW 440 V<br />250 kW 500 V
Factory setting current
361 A
Power dissipation in W
177 W for standard applications
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 3.5 In)
IcL starter rating
410 A connection in the motor supply line for standard applications
IP Degree of Protection
IP00
Assembly style
With heat sink
Function Available
Internal bypass
Supply voltage limits
195…660 V
Supply frequency
50...60 Hz - 10...10 %
Network Frequency
45...66 Hz
Device connection
In the motor supply line
[Uc] control circuit voltage
230 V - 15...10 % 50/60 Hz
Control circuit consumption
20 W
Discrete output number
2
Discrete output type
Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O<br />Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Minimum switching current
100 mA 12 V DC relay outputs)
Maximum switching current
5 A 250 V AC resistive 1 relay outputs<br />5 A 30 V DC resistive 1 relay outputs<br />2 A 250 V AC inductive 0.4 20 ms relay outputs<br />2 A 30 V DC inductive 7 ms relay outputs
Discrete input number
3
Discrete input type
LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Discrete input voltage
24 V <= 30 V
Discrete input logic
Positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA
Output current
0.4...1 Icl adjustable
PTC probe input
750 Ohm
communication port protocol
Modbus
Connector Type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission Rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure line<br />Thermal protection motor<br />Thermal protection starter
marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Height
16.7 in (425 mm)
Width
8.1 in (206 mm)
Depth
11.8 in (299 mm)
Net Weight
72.8 lb(US) (33 kg)
Motor power range AC-3
110…220 kW 380…440 V 3 phase<br />110…220 kW 200…240 V 3 phase<br />250…500 kW 480…500 V 3 phase
Motor starter type
Soft starter
Electromagnetic compatibility
Conducted and radiated emissions level A IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5
Standards
IEC 60947-4-2
Product Certifications
UL<br />CSA<br />CCC<br />C-tick<br />GOST
Vibration resistance
1 gn 13…200 Hz)IEC 60068-2-6<br />1.5 mm 2…13 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Noise level
56 dB
Pollution degree
Level 2 IEC 60664-1
Relative humidity
0…95 % without condensation or dripping water IEC 60068-2-3
Ambient air temperature for operation
14…104 °F (-10…40 °C) without derating)<br />104…140 °F (40…60 °C) with current derating 2.2 % per °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m

Specifications may be subject to change without notice