Product Model

ATS22D32S6U

In Stock
Last updated: 2025/4/30
schneider ATS22D32S6U

Selling Points

  • 1Smoothly accelerates and decelerates asynchronous motors with precise torque control.
  • 2Offers superior thermal protection up to Class 30 for reliable motor operation.
  • 3Automatically manages the bypass function at the end of starting, ensuring electronic protection functions are preserved.
  • 4Compatible with supply voltages from 208V to 600V, supporting a wide range of motor power ratings (7.5 to 25 HP).
  • 5Compact dimensions (130 mm W x 169 mm D x 265 mm H) with IP20 enclosure for easy installation in various environments.
Product Details
ATS22D32S6U
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altistart 22
Product or Component Type
Soft starter
Product destination
Asynchronous motors
Product Specific Application
Pumps and fans
Component name
ATS22
Phase
3 phase
[Us] rated supply voltage
208...600 V - 15...10 %
Maximum Horse Power Rating
10 hp 230 V<br />20 hp 460 V<br />25 hp 575 V<br />7.5 hp 208 V
Factory setting current
27 A
Power dissipation in W
44 W for standard applications
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 3.5 In)
IcL starter rating
32 A connection in the motor supply line for standard applications
IP Degree of Protection
IP20
Assembly style
With heat sink
Function Available
Internal bypass
Supply voltage limits
177…660 V
Supply frequency
50...60 Hz - 10...10 %
Network Frequency
45...66 Hz
Device connection
In the motor supply line
[Uc] control circuit voltage
110 V - 15...10 % 50/60 Hz
Control circuit consumption
20 W
Discrete output number
2
Discrete output type
Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O<br />Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Minimum switching current
100 mA 12 V DC relay outputs)
Maximum switching current
5 A 250 V AC resistive 1 relay outputs<br />5 A 30 V DC resistive 1 relay outputs<br />2 A 250 V AC inductive 0.4 20 ms relay outputs<br />2 A 30 V DC inductive 7 ms relay outputs
Discrete input number
3
Discrete input type
LI1, LI2, LI3) logic, 5 mA 20 kOhm
Discrete input voltage
110 V <= 121 V
Discrete input logic
Positive logic LI1, LI2, LI3 < 20 V <= 15 mA > 79 V, <= 2 mA
Output current
0.4...1 Icl adjustable
PTC probe input
750 Ohm
communication port protocol
Modbus
Connector Type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission Rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure line<br />Thermal protection motor<br />Thermal protection starter
marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Height
10.4 in (265 mm)
Width
5.1 in (130 mm)
Depth
6.7 in (169 mm)
Net Weight
15.4 lb(US) (7 kg)
Electromagnetic compatibility
Conducted and radiated emissions level A IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5
Standards
IEC 60947-4-2
Product Certifications
CCC<br />CSA<br />GOST<br />C-tick<br />UL
Vibration resistance
1 gn 13…200 Hz)IEC 60068-2-6<br />1.5 mm 2…13 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Noise level
45 dB
Pollution degree
Level 2 IEC 60664-1
Relative humidity
0…95 % without condensation or dripping water IEC 60068-2-3
Ambient air temperature for operation
14…104 °F (-10…40 °C) without derating)<br />104…140 °F (40…60 °C) with current derating 2.2 % per °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m

Specifications may be subject to change without notice