Product Model
ATS22D88Q

Selling Points
- 1Efficient Motor Control: The ATS22D88Q soft starter simplifies installation and operation, saving time on wiring and optimizing enclosure size.
- 2Compact Design: With a very compact product design, it minimizes heat dissipation and reduces mechanical stresses on machines.
- 3Integrated Functions: Equipped with bypass and safety functions, protection devices for monitoring, and a simple setup with LEDs, navigation keys, and a 4-digit display.
- 4Versatile Applications: Suitable for asynchronous motors, pumps, fans, and compressors, ensuring a wide range of industrial applications.
- 5Advanced Configuration: Utilize SoMove software for configuring on PC and transferring configurations via Bluetooth or cable, enhancing setup flexibility.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Altistart 22 | Product or Component Type | Soft starter |
Product destination | Asynchronous motors | Product Specific Application | Pumps and fans |
Component name | ATS22 | Phase | 3 phase |
[Us] rated supply voltage | 230...440 V - 15...10 % | Motor power kW | 22 kW 230 V<br />45 kW 400 V<br />45 kW 440 V |
Factory setting current | 81 A | Power dissipation in W | 66 W for standard applications |
Utilisation category | AC-53A | Type of start | Start with torque control (current limited to 3.5 In) |
IcL starter rating | 88 A connection in the motor supply line for standard applications | IP Degree of Protection | IP20 |
Assembly style | With heat sink | Function Available | Internal bypass |
Supply voltage limits | 195…484 V | Supply frequency | 50...60 Hz - 10...10 % |
Network Frequency | 45...66 Hz | Device connection | To the motor delta terminals<br />In the motor supply line |
[Uc] control circuit voltage | 230 V - 15...10 % 50/60 Hz | Control circuit consumption | 20 W |
Discrete output number | 2 | Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O<br />Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
Minimum switching current | 100 mA 12 V DC relay outputs) | Maximum switching current | 5 A 250 V AC resistive 1 relay outputs<br />5 A 30 V DC resistive 1 relay outputs<br />2 A 250 V AC inductive 0.4 20 ms relay outputs<br />2 A 30 V DC inductive 7 ms relay outputs |
Discrete input number | 3 | Discrete input type | LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
Discrete input voltage | 24 V <= 30 V | Discrete input logic | Positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA |
Output current | 0.4...1 Icl adjustable | PTC probe input | 750 Ohm |
communication port protocol | Modbus | Connector Type | 1 RJ45 |
Communication data link | Serial | Physical interface | RS485 multidrop |
Transmission Rate | 4800, 9600 or 19200 bps | Installed device | 31 |
Protection type | Phase failure line<br />Thermal protection motor<br />Thermal protection starter | Marking | CE |
Type of cooling | Forced convection | Operating position | Vertical +/- 10 degree |
Height | 11.6 in (295 mm) | Width | 5.7 in (145 mm) |
Depth | 8.1 in (207 mm) | Net Weight | 26.5 lb(US) (12 kg) |
Motor power range AC-3 | 15…25 kW 200…240 V 3 phase<br />30…50 kW 380…440 V 3 phase | Motor starter type | Soft starter |
Electromagnetic compatibility | Conducted and radiated emissions level A IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5 | Standards | IEC 60947-4-2 |
Product Certifications | CCC<br />CSA<br />UL<br />GOST<br />C-tick | Vibration resistance | 1 gn 13…200 Hz)IEC 60068-2-6<br />1.5 mm 2…13 Hz)IEC 60068-2-6 |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 | Noise level | 45 dB |
Pollution degree | Level 2 IEC 60664-1 | Relative humidity | 0…95 % without condensation or dripping water IEC 60068-2-3 |
Ambient air temperature for operation | 14…104 °F (-10…40 °C) without derating)<br />104…140 °F (40…60 °C) with current derating 2.2 % per °C) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Operating altitude | <= 3280.84 ft (1000 m) without derating<br />> 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m |
Specifications may be subject to change without notice