ATV16U09M2Q
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar 16
Product or Component Type
Variable speed drive
Product destination
Asynchronous motors
[Us] rated supply voltage
200...240 V - 15...10 %
Supply frequency
50/60 Hz +/- 5 %
Network frequency limits
47.5…63 Hz
Phase
1 phase
Motor power kW
0.37 kW
Maximum Horse Power Rating
0.5 hp
Line current
7.3 A 200 V<br />6.1 A 240 V
Apparent power
1 kVA 230 V
Prospective line Isc
1 kA
Continuous output current
3.3 A 200 V<br />3.3 A 240 V
Speed drive output frequency
0.5…400 Hz
Nominal switching frequency
4 kHz
Switching frequency
12...16 kHz with derating factor<br />2...12 kHz adjustable
Local signalling
for DC bus energized 1 LED (red)
Output voltage
<= power supply voltage
communication port protocol
Modbus
Connector Type
1 RJ45
Physical interface
2-wire RS 485
Transmission frame
RTU
Transmission Rate
9600 bps or 19200 bps
Data format
8 bits, 1 stop, odd even or no configurable parity
Height
6.3 in (160 mm)
Width
5.9 in (150 mm)
Depth
4.7 in (120 mm)
Option card
Communication card APOGEE FLN<br />Communication card BACnet<br />Communication card LonWorks<br />Communication card METASYS N2
IP degree of protection
IP31 EN 60530<br />IP31 EN 61800-5-2<br />IP31 IEC 60529<br />IP31 IEC 61800-5-1
Ambient air temperature for operation
14…104 °F (-10…40 °C) without derating)<br />104…122 °F (40…50 °C) with derating factor)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 6561.68 ft (2000 m)<br />3280.84...9842.52 ft (1000...3000 m)

Specifications may be subject to change without notice