Product Model

ATV212WU55N4C

In Stock
Last updated: 2025/4/30
schneider ATV212WU55N4C

Selling Points

  • 1High Efficiency: Achieve energy savings of up to 70% compared to traditional control systems.
  • 2Versatile Application: Suitable for pumps and fans in HVAC systems, ensuring reliable operation.
  • 3Advanced EMC Filter: Integrated Class C1 EMC filter for reduced electromagnetic interference.
  • 4User-Friendly Interface: Centralized technical management with instant viewing of energy consumption.
  • 5Durable Design: IP55 rating for protection against dust and water, ensuring long product lifespan.
Product Details
ATV212WU55N4C
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Device short name
ATV212
Product destination
Asynchronous motors
Phase
3 phase
Motor power kW
5.5 kW
Maximum Horse Power Rating
7.5 hp
Supply voltage limits
323…528 V
Supply frequency
50...60 Hz - 5...5 %
Line current
11 A 380 V<br />8.7 A 480 V
Range of Product
Altivar 212
Product or Component Type
Variable speed drive
Product Specific Application
Pumps and fans in HVAC
communication port protocol
LonWorks<br />METASYS N2<br />APOGEE FLN<br />BACnet<br />Modbus
[Us] rated supply voltage
380...480 V - 15...10 %
EMC filter
Class C1 EMC filter integrated
IP degree of protection
IP55 IEC 61800-5-1<br />IP55 IEC 60529
Apparent power
9.1 kVA 380 V
Continuous output current
12 A 380 V<br />12 A 460 V
Maximum transient current
13.2 A 60 s
Speed drive output frequency
0.5…200 Hz
Speed range
1…10
Speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
Local signalling
for DC bus energized 1 LED (red)
Output voltage
<= power supply voltage
Isolation
Electrical between power and control
Type of cable
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR<br />Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC<br />With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC
Electrical connection
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.004 in² (2.5 mm²) / AWG 14<br />L1/R, L2/S, L3/T terminal 0.009 in² (6 mm²) / AWG 10
Tightening torque
11.5 lbf.in (1.3 N.m), 11.5 lb.in L1/R, L2/S, L3/T)<br />5.3 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection<br />Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection
Sampling duration
2 ms +/- 0.5 ms F discrete<br />2 ms +/- 0.5 ms R discrete<br />2 ms +/- 0.5 ms RES discrete<br />3.5 ms +/- 0.5 ms VIA analog<br />22 ms +/- 0.5 ms VIB analog
Response time
FM 2 ms +/- 0.5 ms analog<br />FLA, FLC 7 ms +/- 0.5 ms discrete<br />FLB, FLC 7 ms +/- 0.5 ms discrete<br />RY, RC 7 ms +/- 0.5 ms discrete
Accuracy
+/- 0.6 % VIA) for a temperature variation 60 °C<br />+/- 0.6 % VIB) for a temperature variation 60 °C<br />+/- 1 % FM) for a temperature variation 60 °C
Linearity error
VIA +/- 0.15 % of maximum value input<br />VIB +/- 0.15 % of maximum value input<br />FM +/- 0.2 % output
Analogue output type
FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits<br />FM switch-configurable current 0...20 mA 970 Ohm 10 bits
Discrete output type
Configurable relay logic FLA, FLC) NO - 100000 cycles<br />Configurable relay logic FLB, FLC) NC - 100000 cycles<br />Configurable relay logic RY, RC) NO - 100000 cycles
Minimum switching current
3 mA 24 V DC configurable relay logic
Maximum switching current
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)<br />5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)<br />2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)<br />2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Discrete input type
F programmable 24 V DC level 1 PLC 4700 Ohm<br />R programmable 24 V DC level 1 PLC 4700 Ohm<br />RES programmable 24 V DC level 1 PLC 4700 Ohm
Discrete input logic
Positive logic (source) F, R, RES), <= 5 V, >= 11 V<br />Negative logic (sink) F, R, RES), >= 16 V, <= 10 V
Dielectric strength
3535 V DC between earth and power terminals<br />5092 V DC between control and power terminals
Insulation resistance
>= 1 mOhm 500 V DC for 1 minute
Frequency resolution
Display unit 0.1 Hz<br />Analog input 0.024/50 Hz
Communication Service
Write multiple registers (16) 2 words maximum<br />Write single register (06)<br />Read holding registers (03) 2 words maximum<br />Time out setting from 0.1 to 100 s<br />Monitoring inhibitable<br />Read device identification (43)
Option card
Communication card LonWorks
Specific application
HVAC
Discrete output number
2
Analogue input number
2
Analogue input type
VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits<br />VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits<br />VIB configurable PTC probe 0...6 probes 1500 Ohm<br />VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Analogue output number
1
Physical interface
2-wire RS 485
Connector Type
1 open style<br />1 RJ45
Transmission Rate
9600 bps or 19200 bps
Transmission frame
RTU
Number of addresses
1…247
Data format
8 bits, 1 stop, odd even or no configurable parity
Type of polarization
No impedance
Asynchronous motor control profile
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)<br />Flux vector control without sensor, standard<br />Voltage/frequency ratio - Energy Saving, quadratic U/f<br />Voltage/frequency ratio, 5 points<br />Voltage/frequency ratio, 2 points
Torque accuracy
+/- 15 %
Transient overtorque
120 % of nominal motor torque +/- 10 % 60 s
Acceleration and deceleration ramps
Automatic based on the load<br />Linear adjustable separately from 0.01 to 3200 s
Motor slip compensation
Adjustable<br />Not available in voltage/frequency ratio motor control<br />Automatic whatever the load
Switching frequency
6...16 kHz adjustable<br />12...16 kHz with derating factor
Nominal switching frequency
12 kHz
Braking to standstill
By DC injection
Network Frequency
47.5...63 Hz
Prospective line Isc
22 kA
Protection type
Overheating protection drive<br />Thermal power stage drive<br />Short-circuit between motor phases drive<br />Input phase breaks drive<br />Overcurrent between output phases and earth drive<br />Overvoltages on the DC bus drive<br />Break on the control circuit drive<br />Against exceeding limit speed drive<br />Line supply overvoltage and undervoltage drive<br />Line supply undervoltage drive<br />Against input phase loss drive<br />Thermal protection motor<br />Motor phase break motor<br />With PTC probes motor
Width
9.06 in (230 mm)
Height
13.4 in (340 mm)
Depth
8.2 in (208 mm)
Net Weight
23.26 lb(US) (10.55 kg)
Pollution degree
3 IEC 61800-5-1
Vibration resistance
1.5 mm 3…13 Hz)IEC 60068-2-6<br />1 gn 13…200 Hz)EN/IEC 60068-2-8
Shock resistance
15 gn 11 ms IEC 60068-2-27
Environmental characteristic
Classes 3C1 IEC 60721-3-3<br />Classes 3S2 IEC 60721-3-3
Noise level
55 dB 86/188/EEC
Operating altitude
3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m<br /><= 3280.84 ft (1000 m) without derating
Relative humidity
5…95 % without condensation IEC 60068-2-3<br />5…95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation
14…104 °F (-10…40 °C) without derating)<br />104…122 °F (40…50 °C) with derating factor)
Operating position
Vertical +/- 10 degree
Product Certifications
NOM 117<br />UL<br />CSA<br />C-tick
marking
CE
Standards
IEC 61800-5-1<br />IEC 61800-5-1<br />IEC 61800-3 environments 2 category C2<br />IEC 61800-3 environments 1 category C2<br />IEC 61800-3<br />IEC 61800-3 category C1<br />IEC 61800-3 environments 2 category C3<br />IEC 61800-3 environments 1 category C2<br />IEC 61800-3 environments 1 category C1<br />IEC 61800-3 environments 2 category C2<br />IEC 61800-3 environments 1 category C3<br />EN 61800-3 category C1<br />EN 55011 group 1 class B<br />IEC 61800-3 environments 1 category C1<br />IEC 61800-3 environments 2 category C1<br />IEC 61800-3 environments 1 category C3<br />IEC 61800-3<br />IEC 61800-3 environments 2 category C3<br />IEC 61800-3 environments 2 category C1
Assembly style
With heat sink
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Voltage dips and interruptions immunity test IEC 61000-4-11
Regulation loop
Adjustable PI regulator
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)

Specifications may be subject to change without notice