Product Model
ATV212WU55N4C

Selling Points
- 1High Efficiency: Achieve energy savings of up to 70% compared to traditional control systems.
- 2Versatile Application: Suitable for pumps and fans in HVAC systems, ensuring reliable operation.
- 3Advanced EMC Filter: Integrated Class C1 EMC filter for reduced electromagnetic interference.
- 4User-Friendly Interface: Centralized technical management with instant viewing of energy consumption.
- 5Durable Design: IP55 rating for protection against dust and water, ensuring long product lifespan.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Device short name | ATV212 | Product destination | Asynchronous motors |
Phase | 3 phase | Motor power kW | 5.5 kW |
Maximum Horse Power Rating | 7.5 hp | Supply voltage limits | 323…528 V |
Supply frequency | 50...60 Hz - 5...5 % | Line current | 11 A 380 V<br />8.7 A 480 V |
Range of Product | Altivar 212 | Product or Component Type | Variable speed drive |
Product Specific Application | Pumps and fans in HVAC | communication port protocol | LonWorks<br />METASYS N2<br />APOGEE FLN<br />BACnet<br />Modbus |
[Us] rated supply voltage | 380...480 V - 15...10 % | EMC filter | Class C1 EMC filter integrated |
IP degree of protection | IP55 IEC 61800-5-1<br />IP55 IEC 60529 | Apparent power | 9.1 kVA 380 V |
Continuous output current | 12 A 380 V<br />12 A 460 V | Maximum transient current | 13.2 A 60 s |
Speed drive output frequency | 0.5…200 Hz | Speed range | 1…10 |
Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn | Local signalling | for DC bus energized 1 LED (red) |
Output voltage | <= power supply voltage | Isolation | Electrical between power and control |
Type of cable | Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR<br />Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC<br />With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC | Electrical connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.004 in² (2.5 mm²) / AWG 14<br />L1/R, L2/S, L3/T terminal 0.009 in² (6 mm²) / AWG 10 |
Tightening torque | 11.5 lbf.in (1.3 N.m), 11.5 lb.in L1/R, L2/S, L3/T)<br />5.3 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) | Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection<br />Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection |
Sampling duration | 2 ms +/- 0.5 ms F discrete<br />2 ms +/- 0.5 ms R discrete<br />2 ms +/- 0.5 ms RES discrete<br />3.5 ms +/- 0.5 ms VIA analog<br />22 ms +/- 0.5 ms VIB analog | Response time | FM 2 ms +/- 0.5 ms analog<br />FLA, FLC 7 ms +/- 0.5 ms discrete<br />FLB, FLC 7 ms +/- 0.5 ms discrete<br />RY, RC 7 ms +/- 0.5 ms discrete |
Accuracy | +/- 0.6 % VIA) for a temperature variation 60 °C<br />+/- 0.6 % VIB) for a temperature variation 60 °C<br />+/- 1 % FM) for a temperature variation 60 °C | Linearity error | VIA +/- 0.15 % of maximum value input<br />VIB +/- 0.15 % of maximum value input<br />FM +/- 0.2 % output |
Analogue output type | FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits<br />FM switch-configurable current 0...20 mA 970 Ohm 10 bits | Discrete output type | Configurable relay logic FLA, FLC) NO - 100000 cycles<br />Configurable relay logic FLB, FLC) NC - 100000 cycles<br />Configurable relay logic RY, RC) NO - 100000 cycles |
Minimum switching current | 3 mA 24 V DC configurable relay logic | Maximum switching current | 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)<br />5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)<br />2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)<br />2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R) |
Discrete input type | F programmable 24 V DC level 1 PLC 4700 Ohm<br />R programmable 24 V DC level 1 PLC 4700 Ohm<br />RES programmable 24 V DC level 1 PLC 4700 Ohm | Discrete input logic | Positive logic (source) F, R, RES), <= 5 V, >= 11 V<br />Negative logic (sink) F, R, RES), >= 16 V, <= 10 V |
Dielectric strength | 3535 V DC between earth and power terminals<br />5092 V DC between control and power terminals | Insulation resistance | >= 1 mOhm 500 V DC for 1 minute |
Frequency resolution | Display unit 0.1 Hz<br />Analog input 0.024/50 Hz | Communication Service | Write multiple registers (16) 2 words maximum<br />Write single register (06)<br />Read holding registers (03) 2 words maximum<br />Time out setting from 0.1 to 100 s<br />Monitoring inhibitable<br />Read device identification (43) |
Option card | Communication card LonWorks | Specific application | HVAC |
Discrete output number | 2 | Analogue input number | 2 |
Analogue input type | VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits<br />VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits<br />VIB configurable PTC probe 0...6 probes 1500 Ohm<br />VIA switch-configurable current 0...20 mA 250 Ohm 10 bits | Analogue output number | 1 |
Physical interface | 2-wire RS 485 | Connector Type | 1 open style<br />1 RJ45 |
Transmission Rate | 9600 bps or 19200 bps | Transmission frame | RTU |
Number of addresses | 1…247 | Data format | 8 bits, 1 stop, odd even or no configurable parity |
Type of polarization | No impedance | Asynchronous motor control profile | Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)<br />Flux vector control without sensor, standard<br />Voltage/frequency ratio - Energy Saving, quadratic U/f<br />Voltage/frequency ratio, 5 points<br />Voltage/frequency ratio, 2 points |
Torque accuracy | +/- 15 % | Transient overtorque | 120 % of nominal motor torque +/- 10 % 60 s |
Acceleration and deceleration ramps | Automatic based on the load<br />Linear adjustable separately from 0.01 to 3200 s | Motor slip compensation | Adjustable<br />Not available in voltage/frequency ratio motor control<br />Automatic whatever the load |
Switching frequency | 6...16 kHz adjustable<br />12...16 kHz with derating factor | Nominal switching frequency | 12 kHz |
Braking to standstill | By DC injection | Network Frequency | 47.5...63 Hz |
Prospective line Isc | 22 kA | Protection type | Overheating protection drive<br />Thermal power stage drive<br />Short-circuit between motor phases drive<br />Input phase breaks drive<br />Overcurrent between output phases and earth drive<br />Overvoltages on the DC bus drive<br />Break on the control circuit drive<br />Against exceeding limit speed drive<br />Line supply overvoltage and undervoltage drive<br />Line supply undervoltage drive<br />Against input phase loss drive<br />Thermal protection motor<br />Motor phase break motor<br />With PTC probes motor |
Width | 9.06 in (230 mm) | Height | 13.4 in (340 mm) |
Depth | 8.2 in (208 mm) | Net Weight | 23.26 lb(US) (10.55 kg) |
Pollution degree | 3 IEC 61800-5-1 | Vibration resistance | 1.5 mm 3…13 Hz)IEC 60068-2-6<br />1 gn 13…200 Hz)EN/IEC 60068-2-8 |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 | Environmental characteristic | Classes 3C1 IEC 60721-3-3<br />Classes 3S2 IEC 60721-3-3 |
Noise level | 55 dB 86/188/EEC | Operating altitude | 3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m<br /><= 3280.84 ft (1000 m) without derating |
Relative humidity | 5…95 % without condensation IEC 60068-2-3<br />5…95 % without dripping water IEC 60068-2-3 | Ambient air temperature for operation | 14…104 °F (-10…40 °C) without derating)<br />104…122 °F (40…50 °C) with derating factor) |
Operating position | Vertical +/- 10 degree | Product Certifications | NOM 117<br />UL<br />CSA<br />C-tick |
marking | CE | Standards | IEC 61800-5-1<br />IEC 61800-5-1<br />IEC 61800-3 environments 2 category C2<br />IEC 61800-3 environments 1 category C2<br />IEC 61800-3<br />IEC 61800-3 category C1<br />IEC 61800-3 environments 2 category C3<br />IEC 61800-3 environments 1 category C2<br />IEC 61800-3 environments 1 category C1<br />IEC 61800-3 environments 2 category C2<br />IEC 61800-3 environments 1 category C3<br />EN 61800-3 category C1<br />EN 55011 group 1 class B<br />IEC 61800-3 environments 1 category C1<br />IEC 61800-3 environments 2 category C1<br />IEC 61800-3 environments 1 category C3<br />IEC 61800-3<br />IEC 61800-3 environments 2 category C3<br />IEC 61800-3 environments 2 category C1 |
Assembly style | With heat sink | Electromagnetic compatibility | Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Voltage dips and interruptions immunity test IEC 61000-4-11 |
Regulation loop | Adjustable PI regulator | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Specifications may be subject to change without notice