Product Model

ATV32H075M2

In Stock
Last updated: 2025/4/29
schneider ATV32H075M2

Selling Points

  • 1High Performance: The ATV32H075M2 offers high performance and improved connectivity, reducing panel space and improving machine efficiency.
  • 2Embedded Bluetooth Technology: Embedded Bluetooth technology enables monitoring, viewing, and performing machine diagnostics without opening cabinet doors.
  • 3Onboard HMI and Navigation Wheel: The drive features an onboard HMI and navigation wheel for easy adjustments, simplifying setup and use.
  • 4Compact Design: The Altivar 32 series is compact, highly energy-efficient, and suitable for conveying applications and other equipment with gear boxes.
  • 5Integrated Safety Functions: Certified to safety standards (SIL 2 according to IEC 61508) and performance level “d” (PL d) according to ISO/EN 13849-1/-2.
Product Details
ATV32H075M2
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar 32
Product or Component Type
Variable speed drive
Product destination
Asynchronous motors<br />Synchronous motors
Product Specific Application
Complex machines
Function Available
-
Assembly style
With heat sink
Component name
ATV32
EMC filter
Class C2 EMC filter integrated
Phase
1 phase
[Us] rated supply voltage
200...240 V - 15...10 %
Supply voltage limits
170…264 V
Supply frequency
50...60 Hz - 5...5 %
Network Frequency
47.5...63 Hz
Motor power kW
0.75 kW 200...240 V
Maximum Horse Power Rating
1 hp 200...240 V
Line current
10.1 A 200 V 1 phase 0.75 kW / 1 hp<br />8.5 A 240 V 1 phase 0.75 kW / 1 hp
Apparent power
2 kVA 240 V 1 phase 0.75 kW / 1 hp
Prospective line Isc
1 kA 1 phase
Nominal output current
4.8 A 4 kHz 240 V 0.75 kW / 1 hp
Maximum transient current
7.2 A 60 s 0.75 kW / 1 hp
Output frequency
0.0005…0.599 kHz
Nominal switching frequency
4 kHz
Switching frequency
2...16 kHz adjustable
Speed range
1…100 asynchronous motor in open-loop mode
Speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
Torque accuracy
+/- 15 %
Transient overtorque
170…200 %
Braking torque
<= 170 % with braking resistor
Asynchronous motor control profile
Voltage/frequency ratio - Energy Saving, quadratic U/f<br />Flux vector control without sensor - Energy Saving, NoLoad law<br />Flux vector control without sensor, standard<br />Voltage/frequency ratio, 5 points<br />Voltage/frequency ratio, 2 points
Synchronous motor control profile
Vector control without sensor
Regulation loop
Adjustable PID regulator
Motor slip compensation
Adjustable 0...300 %<br />Automatic whatever the load<br />Not available in voltage/frequency ratio (2 or 5 points)
Local signalling
1 LED red drive voltage<br />1 LED green CANopen run<br />1 LED red CANopen error<br />1 LED red drive fault
Output voltage
<= power supply voltage
Noise level
43 dB 86/188/EEC
Insulation
Electrical between power and control
Electrical connection
Screw terminal 0.5...1.5 mm², AWG 18...AWG 14 control)<br />Removable screw terminals 1.5...2.5 mm², AWG 14...AWG 12 motor/braking resistor)<br />Screw terminal 1.5...4 mm², AWG 14...AWG 10 power supply)
Tightening torque
4.4 lbf.in (0.5 N.m), 4.4 lb/ft control)<br />6.2 lbf.in (0.7 N.m), 7.1 lb/ft motor/braking resistor)<br />5.3 lbf.in (0.6 N.m), 5.3 lb/ft power supply)
Supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection
Analogue input number
3
Analogue input type
AI1 voltage 0...10 V DC 30000 Ohm 10 bits<br />AI2 bipolar differential voltage +/- 10 V DC 30000 Ohm 10 bits<br />AI3 current 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration) 250 Ohm 10 bits
Sampling duration
2 ms AI1, AI2, AI3) - analog<br />2 ms AO1) - analog
Response time
LI1...LI6 8 ms +/- 0.7 ms logic<br />R1A, R1B, R1C 2 ms relay<br />R2A, R2C 2 ms relay
Accuracy
+/- 0.2 % AI1, AI2, AI3) for a temperature of -10...60 °C<br />+/- 0.5 % AI1, AI2, AI3) for a temperature of 25 °C<br />+/- 1 % AO1) for a temperature of 25 °C<br />+/- 2 % AO1) for a temperature of -10...60 °C
Linearity error
+/- 0.2...0.5 % of maximum value AI1, AI2, AI3)<br />+/- 0.3 % AO1)
Analogue output number
1
Analogue output type
AO1 software-configurable current 0...20 mA 800 Ohm 10 bits<br />AO1 software-configurable voltage 0...10 V 470 Ohm 10 bits
Discrete output number
3
Discrete output type
Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles<br />Configurable relay logic R2A, R2B) NO - 100000 cycles<br />Logic LO)
Minimum switching current
5 mA 24 V DC configurable relay logic
Maximum switching current
R1 3 A 250 V AC resistive, cos phi = 1<br />R1 4 A 30 V DC resistive, cos phi = 1<br />R1, R2 2 A 250 V AC inductive, cos phi = 0.4<br />R1, R2 2 A 30 V DC inductive, cos phi = 0.4<br />R2 5 A 250 V AC resistive, cos phi = 1<br />R2 5 A 30 V DC resistive, cos phi = 1
Discrete input number
7
Discrete input type
Programmable (sink/source) LI1...LI4)24...30 V DC level 1 PLC<br />Programmable as pulse input 20 kpps LI5)24...30 V DC level 1 PLC<br />Switch-configurable PTC probe LI6)24...30 V DC<br />Safe torque off STO)24...30 V DC - 1500 Ohm
Discrete input logic
Negative logic (sink) LI1...LI6), > 19 V, < 13 V<br />Positive logic (source) LI1...LI6), < 5 V, > 11 V
Acceleration and deceleration ramps
Linear<br />CUS<br />Deceleration ramp adaptation<br />Ramp switching<br />S<br />Deceleration ramp automatic stop DC injection<br />U
Braking to standstill
By DC injection
Protection type
Input phase breaks drive<br />Overcurrent between output phases and earth drive<br />Overheating protection drive<br />Short-circuit between motor phases drive<br />Thermal protection drive
communication port protocol
CANopen<br />Modbus
Connector type
1 RJ45 on front face)Modbus/CANopen
Physical interface
2-wire RS 485 Modbus
Transmission frame
RTU Modbus
Type of polarization
No impedance Modbus
Number of addresses
1…127 CANopen<br />1…247 Modbus
Method of access
Slave CANopen
Electromagnetic compatibility
1.2/50 µs - 8/20 µs surge immunity test, level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test, level 3 IEC 61000-4-6<br />Electrical fast transient/burst immunity test, level 4 IEC 61000-4-4<br />Electrostatic discharge immunity test, level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test, level 3 IEC 61000-4-3<br />Voltage dips and interruptions immunity test IEC 61000-4-11
Width
1.8 in (45 mm)
Height
12.8 in (325 mm)
Depth
9.6 in (245 mm)
Net Weight
5.3 lb(US) (2.4 kg)
Option card
Communication card CANopen daisy chain<br />Communication card CANopen open style<br />Communication card DeviceNet<br />Communication card EtherNet/IP<br />Communication card Profibus DP V1
Standards
EN 61800-3 environments 1 category C2<br />EN 55011 class A group 1<br />EN/IEC 61800-5-1<br />EN/IEC 61800-3<br />EN 61800-3 environments 2 category C2
Product Certifications
C-tick<br />NOM 117<br />GOST<br />UL<br />CSA
marking
CE
Pollution degree
2 EN/IEC 61800-5-1
IP degree of protection
IP20 EN/IEC 61800-5-1
Vibration resistance
1 gn 13…200 Hz) EN/IEC 60068-2-6<br />1.5 mm peak to peak 3…13 Hz) EN/IEC 60068-2-6
Shock resistance
15 gn 11 msEN/IEC 60068-2-27
Relative humidity
5…95 % without condensation IEC 60068-2-3<br />5…95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation
14…122 °F (-10…50 °C) without derating<br />122…140 °F (50…60 °C) with derating factor
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />3280.84...6561.68 ft (1000...2000 m) with current derating 1 % per 100 m
Operating position
Vertical +/- 10 degree

Specifications may be subject to change without notice