Product Model

ATV32HU75N4

In Stock
Last updated: 2025/4/28
schneider ATV32HU75N4

Selling Points

  • 17.5 kW (10 HP) for efficient motor control.
  • 2Compatible with 380-500 VAC supply voltage for diverse industrial applications.
  • 3Variable speed control minimizes energy wastage and optimizes energy consumption.
  • 4Built with high-quality components and advanced thermal management for reliable operation in harsh environments.
  • 5Compatible with various control devices and communication protocols for easy integration into existing automation systems.
Product Details
ATV32HU75N4
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar 32
Product or Component Type
Variable speed drive
Product destination
Asynchronous motors<br />Synchronous motors
Product Specific Application
Complex machines
Function Available
-
Assembly style
With heat sink
Component name
ATV32
EMC filter
Class C2 EMC filter integrated
Phase
3 phase
[Us] rated supply voltage
380...500 V - 15...10 %
Supply voltage limits
323…550 V
Supply frequency
50...60 Hz - 5...5 %
Network Frequency
47.5...63 Hz
Motor power kW
7.5 kW 380...480 V
Maximum Horse Power Rating
10 hp 380...480 V
Line current
18.7 A 500 V 3 phase 7.5 kW / 10 hp<br />26.5 A 380 V 3 phase 7.5 kW / 10 hp
Apparent power
22.9 kVA 500 V 3 phase 7.5 kW / 15 hp
Prospective line Isc
22 kA 3 phase
Nominal output current
17 A 4 kHz 500 V 7.5 kW / 10 hp
Maximum transient current
25.5 A 60 s 7.5 kW / 10 hp
Output frequency
0.0005…0.599 kHz
Nominal switching frequency
4 kHz
Switching frequency
2...16 kHz adjustable
Speed range
1…100 asynchronous motor in open-loop mode
Speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
Torque accuracy
+/- 15 %
Transient overtorque
170…200 %
Braking torque
<= 170 % with braking resistor
Asynchronous motor control profile
Flux vector control without sensor, standard<br />Voltage/frequency ratio, 2 points<br />Flux vector control without sensor - Energy Saving, NoLoad law<br />Voltage/frequency ratio, 5 points<br />Voltage/frequency ratio - Energy Saving, quadratic U/f
Synchronous motor control profile
Vector control without sensor
Regulation loop
Adjustable PID regulator
Motor slip compensation
Not available in voltage/frequency ratio (2 or 5 points)<br />Adjustable 0...300 %<br />Automatic whatever the load
Local signalling
1 LED red drive voltage<br />1 LED green CANopen run<br />1 LED red CANopen error<br />1 LED red drive fault
Output voltage
<= power supply voltage
Noise level
43 dB 86/188/EEC
Insulation
Electrical between power and control
Electrical connection
Screw terminal 0.5...1.5 mm², AWG 18...AWG 14 control)<br />Removable screw terminals 2.5...16 mm², AWG 12...AWG 6 motor/braking resistor)<br />Screw terminal 6...16 mm², AWG 8...AWG 6 power supply)
Tightening torque
4.4 lbf.in (0.5 N.m), 4.4 lb/ft control)<br />10.6 lbf.in (1.2 N.m), 10.6 lb/ft motor/braking resistor)<br />10.6 lbf.in (1.2 N.m), 10.6 lb/ft power supply)
Supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection
Analogue input number
3
Analogue input type
AI1 voltage 0...10 V DC 30000 Ohm 10 bits<br />AI2 bipolar differential voltage +/- 10 V DC 30000 Ohm 10 bits<br />AI3 current 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration) 250 Ohm 10 bits
Sampling duration
2 ms AI1, AI2, AI3) - analog<br />2 ms AO1) - analog
Response time
LI1...LI6 8 ms +/- 0.7 ms logic<br />R1A, R1B, R1C 2 ms relay<br />R2A, R2C 2 ms relay
Accuracy
+/- 0.2 % AI1, AI2, AI3) for a temperature of -10...60 °C<br />+/- 0.5 % AI1, AI2, AI3) for a temperature of 25 °C<br />+/- 1 % AO1) for a temperature of 25 °C<br />+/- 2 % AO1) for a temperature of -10...60 °C
Linearity error
+/- 0.2...0.5 % of maximum value AI1, AI2, AI3)<br />+/- 0.3 % AO1)
Analogue output number
1
Analogue output type
AO1 software-configurable current 0...20 mA 800 Ohm 10 bits<br />AO1 software-configurable voltage 0...10 V 470 Ohm 10 bits
Discrete output number
3
Discrete output type
Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles<br />Configurable relay logic R2A, R2B) NO - 100000 cycles<br />Logic LO)
Minimum switching current
5 mA 24 V DC configurable relay logic
Maximum switching current
R1 3 A 250 V AC resistive, cos phi = 1<br />R1 4 A 30 V DC resistive, cos phi = 1<br />R1, R2 2 A 250 V AC inductive, cos phi = 0.4<br />R1, R2 2 A 30 V DC inductive, cos phi = 0.4<br />R2 5 A 250 V AC resistive, cos phi = 1<br />R2 5 A 30 V DC resistive, cos phi = 1
Discrete input number
7
Discrete input type
Programmable (sink/source) LI1...LI4)24...30 V DC level 1 PLC<br />Programmable as pulse input 20 kpps LI5)24...30 V DC level 1 PLC<br />Switch-configurable PTC probe LI6)24...30 V DC<br />Safe torque off STO)24...30 V DC - 1500 Ohm
Discrete input logic
Negative logic (sink) LI1...LI6), > 19 V, < 13 V<br />Positive logic (source) LI1...LI6), < 5 V, > 11 V
Acceleration and deceleration ramps
Deceleration ramp automatic stop DC injection<br />S<br />Linear<br />Ramp switching<br />U<br />CUS<br />Deceleration ramp adaptation
Braking to standstill
By DC injection
Protection type
Input phase breaks drive<br />Overcurrent between output phases and earth drive<br />Overheating protection drive<br />Short-circuit between motor phases drive<br />Thermal protection drive
communication port protocol
CANopen<br />Modbus
Connector type
1 RJ45 on front face)Modbus/CANopen
Physical interface
2-wire RS 485 Modbus
Transmission frame
RTU Modbus
Type of polarization
No impedance Modbus
Number of addresses
1…127 CANopen<br />1…247 Modbus
Method of access
Slave CANopen
Electromagnetic compatibility
1.2/50 µs - 8/20 µs surge immunity test, level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test, level 3 IEC 61000-4-6<br />Electrical fast transient/burst immunity test, level 4 IEC 61000-4-4<br />Electrostatic discharge immunity test, level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test, level 3 IEC 61000-4-3<br />Voltage dips and interruptions immunity test IEC 61000-4-11
Width
5.9 in (150 mm)
Height
12.1 in (308 mm)
Depth
9.1 in (232 mm)
Net Weight
16.5 lb(US) (7.5 kg)
Option card
Communication card CANopen daisy chain<br />Communication card CANopen open style<br />Communication card DeviceNet<br />Communication card EtherNet/IP<br />Communication card Profibus DP V1
Functionality
Mid
Specific application
Other applications
Standards
EN 61800-3 environments 2 category C2<br />EN/IEC 61800-3<br />EN/IEC 61800-5-1<br />EN 61800-3 environments 1 category C2<br />EN 55011 class A group 1
Product Certifications
NOM 117<br />GOST<br />C-tick<br />UL<br />CSA
marking
CE
Pollution degree
2 EN/IEC 61800-5-1
IP degree of protection
IP20 EN/IEC 61800-5-1
Vibration resistance
1 gn 13…200 Hz) EN/IEC 60068-2-6<br />1.5 mm peak to peak 3…13 Hz) EN/IEC 60068-2-6
Shock resistance
15 gn 11 msEN/IEC 60068-2-27
Relative humidity
5…95 % without condensation IEC 60068-2-3<br />5…95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation
14…122 °F (-10…50 °C) without derating<br />122…140 °F (50…60 °C) with derating factor
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m
Operating position
Vertical +/- 10 degree

Specifications may be subject to change without notice