Product Model

ATV340D18N4

In Stock
Last updated: 2025/4/28
schneider ATV340D18N4

Selling Points

  • 1High Performance Motor Control: Optimized for dynamic applications with a speed bandwidth up to 400 Hz.
  • 2Advanced Automation Capabilities: Integrated with cutting-edge application control and easy-to-integrate automation features.
  • 3Robust Design for Harsh Environments: Designed to withstand vibration, shock, and non-conductive dust.
  • 4Integrated EMC Filter: Conforms to EN/IEC 61800-3 category C3 for enhanced electromagnetic compatibility.
  • 5Versatile Communication Options: Supports Modbus serial, Profibus DP V1, Profinet, DeviceNet, CANopen, and EtherCAT protocols.
Product Details
ATV340D18N4
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar Machine ATV340
Product or Component Type
Variable speed drive
Product Specific Application
Machine
Mounting Mode
Cabinet mount
Variant
Standard version
communication port protocol
Modbus serial
Option card
communication module, Profibus DP V1<br /> communication module, PROFINET<br /> communication module, DeviceNet<br /> communication module, CANopen<br /> communication module, EtherCAT
Phase
3 phase
Supply frequency
50...60 Hz +/- 5 %
[Us] rated supply voltage
380...480 V - 15...10 %
Nominal output current
39.0 A
Motor power kW
22 kW normal duty<br />18.5 kW heavy duty
Maximum Horse Power Rating
30 hp normal duty<br />25 hp heavy duty
EMC filter
Class C3 EMC filter integrated
IP degree of protection
IP20
Discrete input number
5
Discrete input type
PTI programmable as pulse input 0…30 kHz, 24 V DC 30 V)<br />DI1...DI5 safe torque off, 24 V DC 30 V)3.5 kOhm<br /> programmable
number of preset speeds
16 preset speeds
Discrete output number
2.0
Discrete output type
Programmable output DQ1, DQ2 30 V DC 100 mA
Analogue input number
2
Analogue input type
AI1 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI1 software-configurable temperature probe or water level sensor<br />AI1 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI2 software-configurable voltage - 10...10 V DC 31.5 kOhm 12 bits
Analogue output number
1
Analogue output type
Software-configurable voltage AQ1 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1 0...20 mA 500 Ohm 10 bits
Relay output number
2
Output voltage
<= power supply voltage
Relay output type
Relay outputs R1A<br />Relay outputs R1C 100000 cycles<br />Relay outputs R2A<br />Relay outputs R2C 100000 cycles
Maximum switching current
Relay output R1C resistive, cos phi = 1 3 A 250 V AC<br />Relay output R1C resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1C inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1C inductive, cos phi = 0.4 7 ms 2 A 30 V DC<br />Relay output R2C resistive, cos phi = 1 5 A 250 V AC<br />Relay output R2C resistive, cos phi = 1 5 A 30 V DC<br />Relay output R2C inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R2C inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Minimum switching current
Relay output R1B 5 mA 24 V DC<br />Relay output R2C 5 mA 24 V DC
Physical interface
2-wire RS 485
Connector Type
1 RJ45
Method of access
Slave Modbus RTU
Transmission Rate
4.8 kbit/s<br />9.6 kbit/s<br />19.2 kbit/s<br />38.4 kbit/s
Transmission frame
RTU
Number of addresses
1…247
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
4 quadrant operation possible
True
Asynchronous motor control profile
Optimized torque mode<br />Variable torque standard<br />Constant torque standard
Synchronous motor control profile
Reluctance motor<br />Permanent magnet motor
Pollution degree
2
Maximum output frequency
0.599 kHz
Acceleration and deceleration ramps
S, U or customized<br />Linear adjustable separately from 0.01...9999 s
Motor slip compensation
Adjustable<br />Automatic whatever the load<br />Can be suppressed<br />Not available in permanent magnet motor law
Switching frequency
2...16 kHz adjustable<br />4...16 kHz with derating factor
Nominal switching frequency
4 kHz
Braking to standstill
By DC injection
Brake chopper integrated
True
Line current
54.7 A 380 V without line choke heavy duty)<br />43.4 A 480 V without line choke heavy duty)<br />49.9 A 380 V with external line choke normal duty)<br />40.2 A 480 V with external line choke normal duty)<br />54.5 A 480 V with external line choke heavy duty)<br />43.5 A 380 V with external line choke heavy duty)
Maximum Input Current per Phase
54.7 A
Maximum output voltage
480 V
Apparent power
33.4 kVA 480 V normal duty)<br />36.1 kVA 480 V heavy duty)
Maximum transient current
50.6 A 60 s normal duty)<br />59 A 60 s heavy duty)<br />62.1 A 2 s normal duty)<br />70 A 2 s heavy duty)
Electrical connection
Control screw terminal 0.2...2.5 mm² AWG 24...AWG 12<br />Line side screw terminal 10...25 mm² AWG 8...AWG 3<br />DC bus screw terminal 10...25 mm² AWG 8...AWG 3<br />Motor screw terminal 6...25 mm² AWG 8...AWG 3
Prospective line Isc
22 kA
Base load current at high overload
39.0 A
Base load current at low overload
46.0 A
Power dissipation in W
Natural convection 21 W 380 V 4 kHz heavy duty)<br />Forced convection 410 W 380 V 4 kHz heavy duty)<br />Natural convection 23 W 380 V 4 kHz normal duty)<br />Forced convection 464 W 380 V 4 kHz normal duty)
With safety function Safely Limited Speed (SLS)
True
With safety function Safe brake management (SBC/SBT)
True
With safety function Safe Operating Stop (SOS)
False
With safety function Safe Position (SP)
False
With safety function Safe programmable logic
False
With safety function Safe Speed Monitor (SSM)
False
With safety function Safe Stop 1 (SS1)
True
With sft fct Safe Stop 2 (SS2)
False
With safety function Safe torque off (STO)
True
With safety function Safely Limited Position (SLP)
False
With safety function Safe Direction (SDI)
False
Protection type
Thermal protection motor<br />Safe torque off motor<br />Motor phase loss motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent drive<br />Output overcurrent between motor phase and earth drive<br />Output overcurrent between motor phases drive<br />Short-circuit between motor phase and earth drive<br />Short-circuit between motor phases drive<br />Motor phase loss drive<br />DC Bus overvoltage drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Input supply loss drive<br />Exceeding limit speed drive<br />Break on the control circuit drive
Width
7.09 in (180.0 mm)
Height
15.2 in (385.0 mm)
Depth
9.8 in (249.0 mm)
Net Weight
22.5 lb(US) (10.2 kg)
Continuous output current
46 A 4 kHz normal duty<br />39 A 4 kHz heavy duty
Operating altitude
<= 9842.52 ft (3000 m) with current derating above 1000m
Operating position
Vertical +/- 10 degree
Product Certifications
UL<br />CSA<br />TÜV<br />EAC<br />CTick
marking
CE
Standards
IEC 61800-3<br />IEC 61800-5-1<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1<br />UL 618000-5-1<br />UL 508C
Assembly style
With heat sink
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3<br />Class 3S3 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)
70 m/s² at 22 ms
Maximum acceleration under vibrational stress (during operation)
5 m/s² at 9...200 Hz
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...9 Hz
Permitted relative humidity (during operation)
Class 3K5 according to EN 60721-3
Volume of cooling air
33814.6 Gal/hr(US) (128.0 m3/h)
Type of cooling
Forced convection
Overvoltage category
Class III
Regulation loop
Adjustable PID regulator
Noise level
56.7 dB
Ambient air transport temperature
-40…158 °F (-40…70 °C)
Ambient air temperature for operation
5…122 °F (-15…50 °C) without derating vertical position)<br />122…140 °F (50…60 °C) with derating factor vertical position)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Isolation
Between power and control terminals

Specifications may be subject to change without notice