Product Model

ATVRD15N4

In Stock
Last updated: 2025/5/1
schneider ATVRD15N4

Selling Points

  • 1High Power Output: 15 kW regenerative unit for efficient energy recovery.
  • 2Robust Design: IEC 60721-3-3 class 3C3 coated printed circuit boards for harsh environments.
  • 3Versatile Connectivity: Compatible with Altivar Machine ATV320, ATV340, and ATV900.
  • 4Advanced Safety Features: Comprehensive embedded safety with Safety Torque Off and four additional safety monitoring functions.
  • 5Durable Construction: Chemical and dust pollution resistance, operating in temperatures from -10°C to 60°C.
Product Details
ATVRD15N4
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar
Range Compatibility
Altivar Machine ATV340<br />Altivar Machine ATV320<br />Altivar Process ATV900
Product or Component Type
Power module
Device Application
Energy regeneration
[Us] rated supply voltage
380...500 V - 15...10 %
[Ue] rated operational voltage
456...778 V DC
Kw Rating
13.5 kW
Network Frequency
45...65 Hz
Phase
3 phase
Fixing Mode
By screws
Maximum voltage drop at rated load
3 %
Electrical connection
Control removable screw terminal block 0.5...1.5 mm², AWG 20...AWG 16 bottom)<br />Power supply removable screw terminal block 6 mm², AWG 8 top)<br />DC bus removable screw terminal block 6 mm², AWG 8 bottom)
Input current
31.8 A 380 V AC voltage inputs continuous)<br />27.9 A 500 V AC voltage inputs continuous)<br />43.1 A 380 V AC voltage inputs transient for 60 s)<br />36.3 A 500 V AC voltage inputs transient for 60 s)
Input power
13.5 kW 380...500 V AC voltage inputs continuous)<br />20.3 kW 380...500 V AC voltage inputs transient for 60 s)
Maximum DC bus voltage
300...880 V DC
Output Current
25.9 A 380 V AC continuous)<br />23.2 A 500 V AC continuous)<br />36.5 A 380 V AC transient for 60 s)<br />29.7 A 500 V AC transient for 60 s)
Width
4.1 in (105 mm)
Height
15.7 in (399 mm)
Depth
9.3 in (235 mm)
Net Weight
25.4 lb(US) (11.5 kg)
Standards
IEC 61800-3<br />IEC 61800-5-1
Product Certifications
cUL
Ambient air temperature for operation
14…122 °F (-10…50 °C) without derating<br />122…140 °F (50…60 °C) with derating factor
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />3280.84...9842.52 ft (1000...3000 m) with power derating 1 % per 100 m
Operating position
Vertical or horizontal position
Type of cooling
Fan
Environmental characteristic
Chemical pollution resistance class 3C3 IEC 60721-3-3<br />Dust pollution resistance class 3S2 IEC 60721-3-3
Pollution degree
2 IEC 61800-5-1

Specifications may be subject to change without notice