Product Model
BMEAHI0812H

Selling Points
- 1The BMEAHI0812H offers 8 isolated HART inputs and 4-20mA current inputs for precise measurement in severe environments.
- 2With 1000V DC isolation between channels and 1400V DC isolation between channels and ground, this module ensures reliable operation.
- 3Designed to operate in temperatures ranging from -13°F to 158°F (-25°C to 70°C), making it suitable for various industrial settings.
- 4Meets CE, UL, CSA, RCM, EAC, and Merchant Navy certifications, ensuring compliance with global safety and performance standards.
- 5Features Schneider Electric's Green Premium label, promising best-in-class environmental performance and compliance with eco-label standards.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon X80 | Product or Component Type | Analog input module |
Application specific I/O | HART | Product Compatibility | BMEP58... processor<br />BMXFTB20... terminal block<br />ABE7CPA31<br />ABE7CPA02<br />ABE7CPA03<br />Head module BMECRA31210<br />BMEXBP... backplane |
Electrical connection | 20 ways terminal block<br /> Telefast | Isolation between channels | Isolated |
Analogue input number | 8 | Analogue input type | Current 4...20 mA |
Analogue input resolution | 15 bits + sign | Input impedance | 250 Ohm internally protective resistor (3.6 to 50 Ohm) |
Measurement error | 0.15 % of full scale 25 °C<br />0.55 % of full scale - 25...70 °C | Temperature drift | 50 ppm/°C |
Isolation voltage | 1000 V DC 60 s between channels<br />1400 V DC 60 s between channels and ground<br />1400 V DC 60 s between channels and bus | Checks | Broken wire detection |
Topology | Point-to-point | Function Available | I/O mapping |
Net Weight | 0.514 lb(US) (0.233 kg) | Ambient Air Temperature for Operation | -13…158 °F (-25…70 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Operating altitude | 0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor |
Directives | 2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility<br />2014/34/EU - ATEX directive | Product certifications | CE<br />UL<br />CSA<br />RCM<br />EAC<br />Merchant Navy<br />ATEX zone 2/22<br />IECEx zone 2/22 |
Standards | EN/IEC 61131-2<br />EN/IEC 61010-2-201<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201<br />IACS E10<br />EN/IEC 61000-6-5, interface type 1 and type 2<br />EN/IEC 61850-3, location G<br />EN/IEC 60079-0 | Environmental characteristic | Gas resistant class Gx ISA S71.04<br />Gas resistant class 3C4 IEC 60721-3-3<br />Dust resistant class 3S4 IEC 60721-3-3<br />Sand resistant class 3S4 IEC 60721-3-3<br />Salt resistant level 2 IEC 68252<br />Mold growth resistant class 3B2 IEC 60721-3-3<br />Fungal spore resistant class 3B2 IEC 60721-3-3<br />Hazardous location class I division 2 |
Protective treatment | Conformal coating |
Specifications may be subject to change without notice