Product Model

BMXART0814

In Stock
Last updated: 2025/4/30
schneider BMXART0814

Selling Points

  • 1High Resolution: 15-bit resolution for precise data capture.
  • 2Isolated Inputs: Ensures reliable operation with channel isolation.
  • 3Compact Design: 40-way connector for easy electrical connection.
  • 4Wide Temperature Range: Operates between 0 to 60°C, suitable for various environments.
  • 5Certified Quality: Meets IEC 61131-2, CSA C22.2 No 142, CSA C22.2 No 213, and UL 508 standards.
Product Details
BMXART0814
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Analog input module
Electrical connection
40 ways 2 connectors
Isolation between channels
Isolated
Input level
Low level
Analogue input number
8
Analogue input type
Voltage +/- 1.28 V<br />Voltage +/- 160 mV<br />Voltage +/- 320 mV<br />Voltage +/- 40 mV<br />Voltage +/- 640 mV<br />Voltage +/- 80 mV<br />Resistor 400 Ohm 2 wires<br />Resistor 400 Ohm 3 wires<br />Resistor 400 Ohm 4 wires<br />Resistor 4000 Ohm 2 wires<br />Resistor 4000 Ohm 3 wires<br />Resistor 4000 Ohm 4 wires<br />Temperature probe -100...+260 °C Cu 10<br />Temperature probe -100...+450 °C Pt 100 UL/JIS<br />Temperature probe -100...+450 °C Pt 1000 UL/JIS<br />Temperature probe -200...+850 °C Pt 100 IEC<br />Temperature probe -200...+850 °C Pt 1000 IEC<br />Temperature probe -60...+180 °C Ni 100<br />Temperature probe -60...+180 °C Ni 1000<br />Thermocouple +130...+1820 °C thermocouple B<br />Thermocouple +270...+1300 °C thermocouple N<br />Thermocouple -200...+600 °C thermocouple U<br />Thermocouple -200...+760 °C thermocouple J<br />Thermocouple -200...+900 °C thermocouple L<br />Thermocouple -270...+1000 °C thermocouple E<br />Thermocouple -270...+1370 °C thermocouple K<br />Thermocouple -270...+400 °C thermocouple T<br />Thermocouple -50...+1769 °C thermocouple R<br />Thermocouple -50...+1769 °C thermocouple S
Analog/digital conversion
Sigma delta 16 bits
Analogue input resolution
15 bits + sign
Permitted overload on inputs
+/- 7.5 V +/- 1.28 V<br />+/- 7.5 V +/- 160 mV<br />+/- 7.5 V +/- 320 mV<br />+/- 7.5 V +/- 40 mV<br />+/- 7.5 V +/- 640 mV<br />+/- 7.5 V +/- 80 mV
Common mode rejection
120 dB 50/60 Hz
Differential mode rejection
60 dB 50/60 Hz
Cold junction compensation
External by Pt100 probe
Type of filter
First order digital filtering
Nominal read cycle time
400 ms with temperature probe<br />200 ms with thermocouple
Measurement error
+/- 0.7 °C Ni 1000 25 °C<br />+/- 2 °C Pt 100 0...60 °C<br />+/- 2 °C Pt 1000 0...60 °C<br />+/- 2.1 °C Ni 100 25 °C<br />+/- 2.1 °C Pt 100 25 °C<br />+/- 2.1 °C Pt 1000 25 °C<br />+/- 2.7 °C thermocouple U 25 °C<br />+/- 2.8 °C thermocouple J 25 °C<br />+/- 3 °C Ni 100 0...60 °C<br />+/- 3 °C thermocouple L 25 °C<br />+/- 3.2 °C thermocouple R 25 °C<br />+/- 3.2 °C thermocouple S 25 °C<br />+/- 3.5 °C thermocouple B 25 °C<br />+/- 3.7 °C thermocouple E 25 °C<br />+/- 3.7 °C thermocouple K 25 °C<br />+/- 3.7 °C thermocouple N 25 °C<br />+/- 3.7 °C thermocouple T 25 °C<br />+/- 4 °C Cu 10 0...60 °C<br />+/- 4 °C Cu 10 25 °C<br />+/- 4.5 °C thermocouple J 0...60 °C<br />+/- 4.5 °C thermocouple L 0...60 °C<br />+/- 4.5 °C thermocouple R 0...60 °C<br />+/- 4.5 °C thermocouple S 0...60 °C<br />+/- 4.5 °C thermocouple U 0...60 °C<br />+/- 5 °C thermocouple B 0...60 °C<br />+/- 5 °C thermocouple E 0...60 °C<br />+/- 5 °C thermocouple K 0...60 °C<br />+/- 5 °C thermocouple N 0...60 °C<br />+/- 5 °C thermocouple T 0...60 °C<br /><= 0.15 % of full scale +/- 1.28 V 0...60 °C<br /><= 0.15 % of full scale +/- 160 mV 0...60 °C<br /><= 0.15 % of full scale +/- 320 mV 0...60 °C<br /><= 0.15 % of full scale +/- 640 mV 0...60 °C<br /><= 0.15 % of full scale +/- 80 mV 0...60 °C<br /><= 0.2 % of full scale 4000 Ohm 0...60 °C<br />0.05 % of full scale +/- 1.28 V 25 °C<br />0.05 % of full scale +/- 160 mV 25 °C<br />0.05 % of full scale +/- 320 mV 25 °C<br />0.05 % of full scale +/- 40 mV 25 °C<br />0.05 % of full scale +/- 640 mV 25 °C<br />0.05 % of full scale +/- 80 mV 25 °C<br />0.12 % of full scale 400 Ohm 25 °C<br />0.12 % of full scale 4000 Ohm 25 °C<br /><= 0.2 % of full scale +/- 40 mV 0...60 °C<br /><= 0.3 % of full scale 400 Ohm 0...60 °C<br />1.3 °C Ni 1000 0...60 °C
Temperature drift
25 ppm/°C 400 Ohm<br />25 ppm/°C 4000 Ohm<br />25 ppm/°C Ni 1000<br />25 ppm/°C thermocouple B<br />25 ppm/°C thermocouple E<br />25 ppm/°C thermocouple J<br />25 ppm/°C thermocouple K<br />25 ppm/°C thermocouple L<br />25 ppm/°C thermocouple N<br />25 ppm/°C thermocouple R<br />25 ppm/°C thermocouple S<br />25 ppm/°C thermocouple T<br />25 ppm/°C thermocouple U<br />30 ppm/°C +/- 1.28 V<br />30 ppm/°C +/- 160 mV<br />30 ppm/°C +/- 320 mV<br />30 ppm/°C +/- 40 mV<br />30 ppm/°C +/- 640 mV<br />30 ppm/°C +/- 80 mV<br />30 ppm/°C Cu 10<br />30 ppm/°C Ni 100<br />30 ppm/°C Pt 100<br />30 ppm/°C Pt 1000
Recalibration
Internal
Detection type
Open circuit Cu 10<br />Open circuit Ni 100<br />Open circuit Ni 1000<br />Open circuit Pt 100<br />Open circuit Pt 1000<br />Open circuit thermocouple B<br />Open circuit thermocouple E<br />Open circuit thermocouple J<br />Open circuit thermocouple K<br />Open circuit thermocouple L<br />Open circuit thermocouple N<br />Open circuit thermocouple R<br />Open circuit thermocouple S<br />Open circuit thermocouple T<br />Open circuit thermocouple U
Maximum wiring resistance
20 Ohm 2 wires Cu 10<br />20 Ohm 2 wires Ni 100<br />20 Ohm 2 wires Pt 100<br />20 Ohm 3 wires Cu 10<br />20 Ohm 3 wires Ni 100<br />20 Ohm 3 wires Pt 100<br />200 Ohm 2 wires Ni 1000<br />200 Ohm 2 wires Pt 1000<br />200 Ohm 3 wires Ni 1000<br />200 Ohm 3 wires Pt 1000<br />50 Ohm 4 wires Cu 10<br />50 Ohm 4 wires Ni 100<br />50 Ohm 4 wires Pt 100<br />500 Ohm 4 wires Ni 1000<br />500 Ohm 4 wires Pt 1000
Measurement resolution
0.1 °C Cu 10<br />0.1 °C Ni 100<br />0.1 °C Ni 1000<br />0.1 °C Pt 100<br />0.1 °C Pt 1000<br />0.1 °C thermocouple B<br />0.1 °C thermocouple E<br />0.1 °C thermocouple J<br />0.1 °C thermocouple K<br />0.1 °C thermocouple L<br />0.1 °C thermocouple N<br />0.1 °C thermocouple R<br />0.1 °C thermocouple S<br />0.1 °C thermocouple T<br />0.1 °C thermocouple U<br />1280/2exp14 mV +/- 1.28 V<br />160/2exp14 mV +/- 160 mV<br />320/2exp14 mV +/- 320 mV<br />40/2exp14 mV +/- 40 mV<br />12.5 mOhm 400 Ohm<br />125 mOhm 4000 Ohm<br />640/2exp14 mV +/- 640 mV<br />80/2exp14 mV +/- 80 mV
Maximum conversion value
+/- 100 % 400 Ohm<br />+/- 100 % 4000 Ohm<br />+/- 102.5 % +/- 1.28 V<br />+/- 102.5 % +/- 160 mV<br />+/- 102.5 % +/- 320 mV<br />+/- 102.5 % +/- 40 mV<br />+/- 102.5 % +/- 640 mV<br />+/- 102.5 % +/- 80 mV
MTBF reliability
900000 H
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor
Status LED
1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O
Net Weight
0.364 lb(US) (0.165 kg)
Current consumption
150 mA 3.3 V DC<br />50 mA 24 V DC
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Product Certifications
CE<br />EAC<br />UL<br />CSA<br />Merchant Navy<br />RCM
Standards
IEC 61131-2<br />IEC 61000-6-4<br />IEC 61000-6-2<br />EN 61010-2-201
Environmental characteristic
3C3 IEC 60721-3-3<br />3C4 IEC 60721-3-3

Specifications may be subject to change without notice