schneider GV2LE03

Selling Points

  • 1Magnetic Protection: Provides magnetic protection with a tripping level at 13xIn for enhanced safety.
  • 2High Breaking Capacity: Features a high breaking capacity of 100kA, ensuring reliable operation under short-circuit conditions.
  • 3Toggle Control: Equipped with a toggle switch for start-stop control, guaranteed for 100,000 cycles AC-3.
  • 4Multi-Standard Certified: Meets multiple international standards including IEC, UL, CSA, CCC, EAC, and Marine certifications.
  • 5Durable Design: Constructed with durable materials, suitable for 100,000 cycles of mechanical and electrical durability.
Product Details
GV2LE03
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2LE
Device Application
Motor protection
Trip unit technology
Magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2<br />AC-3 IEC 60947-4-1<br />AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-2
Motor power kW
0.09 kW 400/415 V AC 50/60 Hz<br />0.06 kW 400/415 V AC 50/60 Hz
Breaking capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 440 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 500 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2<br />100 % 400/415 V AC 50/60 Hz IEC 60947-2<br />100 % 440 V AC 50/60 Hz IEC 60947-2<br />100 % 500 V AC 50/60 Hz IEC 60947-2<br />100 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Toggle
Line Rated Current
0.4 A
Thermal protection adjustment range
0.25…0.4 A IEC 60947-4-1
Magnetic tripping current
5.8 A
[Ith] conventional free air thermal current
0.4 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
1.8 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In<br />100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clipped<br />Panel screwed with adaptor plate)
Mounting position
Horizontal<br />Vertical
Width
1.8 in (45 mm)
Height
3.5 in (89 mm)
Depth
3.09 in (78.5 mm)
Net Weight
0.73 lb(US) (0.33 kg)
color
Dark grey
Standards
EN/IEC 60947-2<br />EN/IEC 60947-4-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />IEC/EN 60335-2-40:Annex JJ
Product Certifications
CCC<br />UL<br />CSA<br />EAC<br />LROS (Lloyds register of shipping)<br />BV<br />RINA<br />DNV-GL<br />UKCA<br />IECEE CB Scheme
IK degree of protection
IK04
IP degree of protection
IP20 IEC 60529
Climatic withstand
IACS E10
Ambient Air Temperature for Storage
-40…176 °F (-40…80 °C)
Fire resistance
1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation
-4…140 °F (-20…60 °C)
Mechanical robustness
Shocks 30 Gn for 11 ms<br />Vibrations 5 Gn, 5...150 Hz
Operating altitude
6561.68 ft (2000 m)

Specifications may be subject to change without notice