schneider GV2RT05

Selling Points

  • 1High-Performance Thermal Overload Relay: Ensures reliable motor protection with advanced thermal and magnetic trip technology.
  • 2Compact and Efficient Design: Seamlessly integrates into your electrical system with a compact footprint.
  • 3Wide Power Rating Range: Supports 0.09 to 1 kW power ratings for versatile application use.
  • 4Robust Construction: Withstands mechanical shocks and vibrations, ensuring durability in harsh environments.
  • 5Compliant with International Standards: Meets IEC 60947-2 and IEC 60947-4-1 standards for safety and performance.
Product Details
GV2RT05
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2RT
Device Application
Motor protection<br />Transformer
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2<br />AC-3 IEC 60947-4-1<br />AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-4-1
Motor power kW
0.09 kW 220/230 V AC 50/60 Hz motor protection high peak current<br />0.12 kW 220/230 V AC 50/60 Hz motor protection high peak current<br />0.25 kW 400/415 V AC 50/60 Hz motor protection high peak current<br />0.37 kW 400/415 V AC 50/60 Hz motor protection high peak current<br />0.25 kW 440 V AC 50/60 Hz motor protection high peak current<br />0.37 kW 440 V AC 50/60 Hz motor protection high peak current<br />0.37 kW 500 V AC 50/60 Hz motor protection high peak current<br />0.55 kW 690 V AC 50/60 Hz motor protection high peak current<br />0.63 kW 440 V AC 50/60 Hz transformer protection<br />0.63 kW 500 V AC 50/60 Hz transformer protection<br />1 kW 690 V AC 50/60 Hz transformer protection
Breaking capacity
100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 440 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 500 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Control Type
Toggle
Line Rated Current
1 A
Thermal protection adjustment range
0.63…1 A IEC 60947-4-1
Magnetic tripping current
22 A
[Ith] conventional free air thermal current
1 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In<br />100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clipped<br />Panel screwed with adaptor plate)
Mounting position
Horizontal<br />Vertical
Width
1.8 in (45 mm)
Height
3.5 in (89 mm)
Depth
3.09 in (78.5 mm)
Standards
EN/IEC 60947-2<br />EN/IEC 60947-4-1
Product Certifications
CCC<br />UL<br />CSA<br />EAC<br />LROS (Lloyds register of shipping)<br />BV<br />UKCA
IK degree of protection
IK04
IP degree of protection
IP20 IEC 60529
Climatic withstand
IACS E10
Ambient Air Temperature for Storage
-40…176 °F (-40…80 °C)
Fire resistance
1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation
-4…140 °F (-20…60 °C)
Mechanical robustness
Shocks 30 Gn for 11 ms<br />Vibrations 5 Gn, 5...150 Hz
Operating altitude
6561.68 ft (2000 m)

Specifications may be subject to change without notice