Product Model
GV2RT14

Selling Points
- 1Designed for continuous operation in AC-3 applications, ensuring reliable motor protection.
- 2Provides comprehensive thermal and magnetic protection against overcurrents and short circuits.
- 3Easy installation on 35 mm symmetrical DIN rail or panel mounting with an adaptor plate.
- 4Compatible with 220/230 V AC, 400/415 V AC, and 440 V AC, covering various motor power needs.
- 5Offers a high breaking capacity of up to 100 kA at 220/230 V AC and 15 kA at 440 V AC for robust protection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range | TeSys Deca | Product name | TeSys GV2 |
Product or Component Type | Motor circuit breaker | Device short name | GV2RT |
Device Application | Motor protection<br />Motor | Trip unit technology | Thermal-magnetic |
Poles description | 3P | Network type | AC |
Utilisation category | Category A IEC 60947-2<br />AC-3 IEC 60947-4-1<br />AC-3e IEC 60947-4-1 | Network frequency | 50/60 Hz IEC 60947-4-1 |
Motor power kW | 1.5 kW 220/230 V AC 50/60 Hz motor protection high peak current<br />2.2 kW 220/230 V AC 50/60 Hz motor protection high peak current<br />3 kW 400/415 V AC 50/60 Hz motor protection high peak current<br />4 kW 400/415 V AC 50/60 Hz motor protection high peak current<br />4 kW 440 V AC 50/60 Hz motor protection high peak current<br />4 kW 500 V AC 50/60 Hz motor protection high peak current<br />5.5 kW 500 V AC 50/60 Hz motor protection high peak current<br />5.5 kW 690 V AC 50/60 Hz motor protection high peak current<br />7.5 kW 690 V AC 50/60 Hz motor protection high peak current<br />2.5 kW 230/240 V AC 50/60 Hz transformer protection<br />4 kW 400/415 V AC 50/60 Hz transformer protection<br />5 kW 400/415 V AC 50/60 Hz transformer protection<br />5 kW 440 V AC 50/60 Hz transformer protection<br />5 kW 500 V AC 50/60 Hz transformer protection<br />6.3 kW 500 V AC 50/60 Hz transformer protection | Breaking capacity | 100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2<br />100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2<br />15 kA Icu 440 V AC 50/60 Hz IEC 60947-2<br />10 kA Icu 500 V AC 50/60 Hz IEC 60947-2<br />3 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
Control Type | Toggle | Line Rated Current | 10 A |
Thermal protection adjustment range | 6…10 A IEC 60947-4-1 | Magnetic tripping current | 200 A |
[Ith] conventional free air thermal current | 10 A IEC 60947-4-1 | [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 | [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
Suitability for isolation | Yes IEC 60947-1 | Power dissipation per pole | 2.5 W |
Mechanical durability | 100000 cycles | Electrical durability | 100000 cycles AC-3 415 V In<br />100000 cycles AC-3e 415 V In |
Rated duty | Continuous IEC 60947-4-1 | Tightening torque | 15.05 lbf.in (1.7 N.m) screw clamp terminal |
Fixing mode | 35 mm symmetrical DIN rail clipped<br />Panel screwed with adaptor plate) | Mounting position | Horizontal<br />Vertical |
Width | 1.8 in (45 mm) | Height | 3.5 in (89 mm) |
Depth | 3.09 in (78.5 mm) | Standards | EN/IEC 60947-2<br />EN/IEC 60947-4-1 |
Product Certifications | CCC<br />UL<br />CSA<br />EAC<br />LROS (Lloyds register of shipping)<br />BV<br />UKCA | IK degree of protection | IK04 |
IP degree of protection | IP20 IEC 60529 | Climatic withstand | IACS E10 |
Ambient Air Temperature for Storage | -40…176 °F (-40…80 °C) | Fire resistance | 1760 °F (960 °C) IEC 60695-2-11 |
Ambient air temperature for operation | -4…140 °F (-20…60 °C) | Mechanical robustness | Shocks 30 Gn for 11 ms<br />Vibrations 5 Gn, 5...150 Hz |
Operating altitude | 6561.68 ft (2000 m) |
Specifications may be subject to change without notice