Product Model
HMIST6400

Selling Points
- 1High-resolution 7-inch LCD display with 800 x 480 pixel resolution.
- 2Multi-port connectivity: 1 COM1 Serial Link, 1 COM2 Serial Link, 2 Ethernet, and USB 2.0 Type A and Micro B.
- 3Robust software: EcoStruxure Operator Terminal Expert with multi-screen and layout objects for easy operation.
- 4Long-lasting components: 100,000 times resistive touch panel and 50,000+ hour LED backlight.
- 5Enhanced cybersecurity with application to firmware level protection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Harmony ST6 | Product or Component Type | Touch panel screen |
Software package | EcoStruxure Operator Terminal Expert | Processor name | ARM Cortex-A8 |
Processor frequency | 800 MHz | Memory description | 1 GB device memory<br />128 MB user data memory<br />512 KB backup memory |
Display size | 7 inch | Display Type | Colour TFT LCD |
Display colour | 16 million colours | Display Resolution | 800 x 480 pixels WVGA |
Touch panel | Single touch analogue resistive | Backlight lifespan | 50000 hours white |
Brightness | 16 levels | Character font | ASCII<br />ASCII (European characters)<br />Chinese (simplified Chinese)<br />Japanese (ANK, Kanji)<br />Katakana<br />Korean<br />Taiwanese (traditional Chinese) |
[Us] rated supply voltage | 24 V DC +/- 20 %) | Power consumption in W | 9 W |
Inrush current | 30 A | Local signalling | Status LED green, steady offline<br />Status LED green, steady operating<br />Status LED green, flashing operating<br />Status LED green, faded stand-by<br />Status LED orange, flashing software starting up<br />Status LED red, steady power supply (ON)<br />Status LED red, flashing operating<br />Status LED red, off power supply (OFF) |
Number of pages | 200 application pages | Port Ethernet | 10/100BASE |
Integrated connection type | 1 COM1 serial link - 1 SUB-D 9-pin female - RS232C 2400...115200 bps)bottom<br />1 COM2 serial link - female RJ45 - RS485 2400...115200 bps)back<br /> COM2 serial link 2400...187500 bps)back<br />1 USB 2.0 type Abottom<br />1 USB 2.0 type micro B<br />2 Ethernet | Supply | External supply |
Realtime clock | Built-in 0...50 °C<br />Built-in 10...90 % RH | Downloadable protocols | Modbus<br />Uni-TE<br />Third party protocols |
Product brand | Schneider Electric Modicon<br />Mitsubishi Melsec<br />Omron Sysmac<br />Rockwell Automation Allen-Bradley<br />Siemens Simatic | Fixing mode | By 4 screws 1.6...5 mm thick panel UL 61010-2-201<br />By 4 screws IEC 61131-2<br />By 4 screws IEC 61000-6-2 |
Enclosure Material | PC | Front material | Aluminium |
marking | CE | Cut-out dimensions | 190 x 135 mm panel cut dimension |
Height | 6.02 in (153 mm) | Width | 8.2 in (208 mm) |
Depth | 1.8 in (45 mm) | Net Weight | 1.8 lb(US) (0.8 kg) |
Immunity to microbreaks | 5 ms | Standards | IEC 61000-6-4<br />IEC 61000-6-2<br />IEC 61131-2<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201 |
Product Certifications | CSA<br />CE<br />UKCA | Directives | 2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility |
Ambient Air Temperature for Operation | 32…122 °F (0…50 °C) | Ambient Air Temperature for Storage | -4…140 °F (-20…60 °C) |
Relative humidity | 10…90 % non-condensing | Operating altitude | 6561.68 ft (2000 m) |
IP degree of protection | IP20 IEC 61131-2 rear panel)<br />IP65 IEC 61131-2 front panel) | NEMA degree of protection | NEMA 4 front panel (indoor use)<br />NEMA 13 front panel (in enclosure) |
Shock resistance | 147 m/s² 11 ms X, Y, Z directions for 3 times)IEC 61131-2 | Vibration resistance | +/- 3.5 mm 5…9 Hz) X, Y, Z directions for 10 cycles (approx. 100 min) IEC 61131-2<br />9.8 m/s² 9…150 Hz) |
Electromagnetic compatibility | Electrical fast transient/burst immunity test - test level: 2 kV (power ports) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 1 kV (signal ports)<br />Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 level 3<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) |