schneider LC1D40008L6

Selling Points

  • 1High current rating: 60 A at 575 VAC.
  • 2Efficient coil power: 140 VA inrush, 13 VA hold-in.
  • 3Versatile voltage compatibility: 120, 120/690 VAC, 300 VDC.
  • 4Reliable contact configuration: 2NO-2NC.
  • 5Durable and compact design: 127 mm H x 85 mm W x 125 mm D.
Product Details
LC1D40008L6
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit 690 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <140 °F (60 °C)) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
200 V AC 60 Hz
Motor power kW
18.5 kW at 380...400 V AC 50/60 Hz<br />22 kW at 500 V AC 50/60 Hz<br />30 kW at 660...690 V AC 50/60 Hz<br />22 kW at 415...440 V AC 50/60 Hz<br />11 kW at 220...230 V AC 50/60 Hz
Maximum Horse Power Rating
10 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA<br />10 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to UL<br />10 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to CSA<br />10 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to UL<br />3 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA<br />3 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL<br />30 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to CSA<br />30 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to UL<br />30 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to CSA<br />30 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to UL<br />5 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA<br />5 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit<br />40 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
800 A at 440 V AC for power circuit conforming to IEC 60947<br />140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
800 kA at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1<br />80 A at 690 V coordination type 1 for power circuit<br />80 A at 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
5.4 W AC-1<br />2.4 W AC-3
[Ui] rated insulation voltage
Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-4-1<br />Power circuit 690 V IEC 60947-4-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
15000000 cycles
Control circuit type
AC 60 Hz
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.6 Uc 140 °F (60 °C) drop-out AC 50/60 Hz<br />0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz
Inrush power in VA
140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C))
Heat dissipation
2…3 W at 50/60 Hz for control circuit
Operating time
4...19 ms opening<br />12...22 ms closing
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminal 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: solid with cable end<br />Power circuit: screw clamp terminal 2 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: solid with cable end<br />Power circuit: screw clamp terminal 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminal 2 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminal 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminal 2 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible with cable end
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 6 mm hexagonal<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal Philips No 2 hexagonal
Auxiliary contact composition
2 NO + 2 NC
Auxiliary contacts type
Mirror contact 1 NC IEC 60947-4-1<br />Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Plate<br />Rail
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 508<br />CSA C22.2 No 14
Product Certifications
RINA<br />UL<br />LROS (Lloyds register of shipping)<br />CSA<br />CCC<br />GL<br />DNV<br />BV
IP degree of protection
IP2X VDE 0106
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating
Operating altitude
9842.52 ft (3000 m) without derating
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor opened 10 Gn) <br />Shocks contactor closed 15 gn) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz)
Net Weight
3.17 lb(US) (1.44 kg)

Specifications may be subject to change without notice