schneider LC1F400

Selling Points

  • 1The LC1F400 contactor is designed to withstand 2400 cycles/hour, ensuring long mechanical and electrical life.
  • 2TeSys F contactors provide consistent low-voltage architecture, ensuring safe and reliable operation in various industrial settings.
  • 3Suitable for motor control, resistive load applications, and integration in control systems, making it versatile for multiple industrial uses.
  • 4Meets international standards including IEC, CCC, CSA, and UL certifications for enhanced reliability and safety.
  • 5Drawer-mounted coils allow for easy maintenance and reduce downtime, ensuring minimal disruption to operations.
Product Details
LC1F400
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-1<br />AC-4
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
500 A 104 °F (40 °C)) <= 440 V AC AC-1<br />400 A 131 °F (55 °C)) <= 440 V AC AC-3
Motor power kW
185 kW at 1000 V AC 50/60 Hz (AC-3)<br />200 kW at 380...400 V AC 50/60 Hz (AC-3)<br />220 kW at 415 V AC 50/60 Hz (AC-3)<br />250 kW at 440 V AC 50/60 Hz (AC-3)<br />257 kW at 500 V AC 50/60 Hz (AC-3)<br />110 kW at 220...240 V AC 50/60 Hz (AC-3)<br />280 kW at 660...690 V AC 50/60 Hz (AC-3)<br />75 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage
48...1000 V AC 40...400 Hz with LX1/LX9 coil<br />48...440 V DC with LX4 coil<br />100...250 V AC 50/60 Hz with LXE coil<br />100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
500 A (at 104 °F (40 °C))
Irms rated making capacity
4000 A AC conforming to IEC 60947-4-1
Rated breaking capacity
3200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
3600 A 104 °F (40 °C) - 10 s<br />2400 A 104 °F (40 °C) - 30 s<br />1700 A 104 °F (40 °C) - 1 min<br />1200 A 104 °F (40 °C) - 3 min<br />1000 A 104 °F (40 °C) - 10 min
Associated fuse rating
400 A aM at <= 440 V<br />500 A gG at <= 440 V
Average impedance
0.26 mOhm - Ith 500 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
65 W AC-1<br />42 W AC-3
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil<br />Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.2...0.35 Uc DC with LX4 coil<br />Operational: 85...275 V AC 50/60 Hz with LXE coil<br />Drop-out: 0...60 V AC 50/60 Hz with LXE coil<br />Operational: 85...418 V DC with LXE coil<br />Drop-out: 0...45 V DC with LXE coil
Heat dissipation
14 W<br />2.2…5.5 W
Operating time
40...75 ms closing with LX1/LX9 coil<br />100...170 ms opening with LX1/LX9 coil<br />50...60 ms closing with LX4 coil<br />45...60 ms opening with LX4 coil<br />40...80 ms closing with LXE coil<br />6...54 ms opening with LXE coil
Mounting Support
Plate
Standards
JIS C8201-4-1<br />IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-4-1<br />EN 60947-1
Product Certifications
CB<br />ABS<br />DNV<br />RMRoS<br />LROS (Lloyds register of shipping)<br />BV<br />RINA<br />UL<br />CSA<br />UKCA
Connections - terminals
Power circuit bar 2 30 x 5 mm<br />Power circuit lugs-ring terminals 2 0.2 in² (150 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1.0 0.0004…0.004 in² (0.25…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)solid without cable end
Tightening torque
Power circuit 309.8 lbf.in (35 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)<br />Control circuit 5.3 lbf.in (0.6 N.m)
Mechanical durability
10 Mcycles
Inrush power in VA
1000…1150 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />920…1140 VA (at 68 °F (20 °C))with LX4 coil<br />360…470 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />410…450 VA (at 68 °F (20 °C))with LXE coil
Hold-in power consumption in VA
12…18 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />4…7.5 VA (at 68 °F (20 °C))with LX4 coil<br />4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />2.5…4.0 VA (at 68 °F (20 °C))with LXE coil
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open1.5 Gn, 5...300 Hz<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
8.1 in (206 mm)
Width
8.4 in (213 mm)
Depth
8.6 in (219 mm)
Net Weight
17.6 lb(US) (8 kg)

Specifications may be subject to change without notice