schneider LC1F4004

Selling Points

  • 1High Power Rating: Handles up to 500A at 440V AC-1.
  • 2Versatile Coil Options: Compatible with LXE coil (100-250V AC/DC), LX1/LX9 coil (48-1000V AC/40-400Hz), and LX4 coil (48-440V DC).
  • 3Robust Construction: Designed for 10 million mechanical cycles and 2400 cycles/hour at 55°C.
  • 4Wide Voltage Range: Operates at 100-250V AC/DC, 48-1000V AC/40-400Hz, and 48-440V DC.
  • 5Reliable Insulation: Meets IEC 60947-4-1 standards with a rated insulation voltage of 1000V AC and 1500V DC.
Product Details
LC1F4004
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
power pole contact composition
4 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
500 A 104 °F (40 °C)) <= 440 V AC AC-1
[Uc] control circuit voltage
48...1000 V AC 40...400 Hz with LX1/LX9 coil<br />48...440 V DC with LX4 coil<br />100...250 V AC 50/60 Hz with LXE coil<br />100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
500 A (at 104 °F (40 °C))
Irms rated making capacity
4000 A AC conforming to IEC 60947-4-1
Rated breaking capacity
3200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
3600 A 104 °F (40 °C) - 10 s<br />2400 A 104 °F (40 °C) - 30 s<br />1700 A 104 °F (40 °C) - 1 min<br />1200 A 104 °F (40 °C) - 3 min<br />1000 A 104 °F (40 °C) - 10 min
Associated fuse rating
400 A aM at <= 440 V<br />500 A gG at <= 440 V
Average impedance
0.26 mOhm - Ith 500 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
65 W AC-1
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil<br />Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.2...0.35 Uc DC with LX4 coil<br />Operational: 85...275 V AC 50/60 Hz with LXE coil<br />Drop-out: 0...60 V AC 50/60 Hz with LXE coil<br />Operational: 85...418 V DC with LXE coil<br />Drop-out: 0...45 V DC with LXE coil
Heat dissipation
14 W<br />2.2…5.5 W
Operating time
40...75 ms closing with LX1/LX9 coil<br />100...170 ms opening with LX1/LX9 coil<br />50...60 ms closing with LX4 coil<br />45...60 ms opening with LX4 coil<br />40...80 ms closing with LXE coil<br />6...54 ms opening with LXE coil
Mounting Support
Plate
Standards
JIS C8201-4-1<br />IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-4-1<br />EN 60947-1
Product Certifications
CB<br />ABS<br />DNV<br />RMRoS<br />LROS (Lloyds register of shipping)<br />BV<br />RINA<br />UL<br />CSA<br />UKCA
Connections - terminals
Power circuit bar 2 30 x 5 mm<br />Power circuit lugs-ring terminals 2 0.2 in² (150 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1.0 0.0004…0.004 in² (0.25…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)solid without cable end
Tightening torque
Power circuit 309.8 lbf.in (35 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)<br />Control circuit 5.3 lbf.in (0.6 N.m)
Mechanical durability
10 Mcycles
Inrush power in VA
1000…1150 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />920…1140 VA (at 68 °F (20 °C))with LX4 coil<br />360…470 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />410…450 VA (at 68 °F (20 °C))with LXE coil
Hold-in power consumption in VA
12…18 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />4…7.5 VA (at 68 °F (20 °C))with LX4 coil<br />4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />2.5…4.0 VA (at 68 °F (20 °C))with LXE coil
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open1.5 Gn, 5...300 Hz<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
8.1 in (206 mm)
Width
10.3 in (261 mm)
Depth
8.6 in (219 mm)
Net Weight
17.6 lb(US) (8 kg)