schneider LC1G8004LSEA

Selling Points

  • 1High current rating: 800A at <=440V AC-1 and 1050A at <=1000V AC-1.
  • 2Wide voltage range: 200-500V AC/DC coil for versatile applications.
  • 3Advanced insulation: Complementary [Uimp] rated impulse withstand voltage of 8 kV.
  • 4Robust construction: Built-in bidirectional peak limiting and high mechanical durability.
  • 5Compliance with standards: Meets EN/IEC 60947-4-1, EN/IEC 60947-5-1, and other international standards.
Product Details
LC1G8004LSEA
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Giga
Product or Component Type
Contactor
Device short name
LC1G
Contactor application
Power switching
Utilisation category
AC-3<br />AC-3e<br />AC-1<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />DC-1<br />DC-3<br />DC-5
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
800 A (at <140 °F (60 °C)) at <= 440 V AC-3<br />1050 A (at <104 °F (40 °C)) at <= 1000 V AC-1
[Uc] control circuit voltage
200...500 V AC 50/60 Hz<br />200...500 V DC
Control circuit voltage limits
Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
1050 A (at 104 °F (40 °C))
Rated breaking capacity
5870 A at 440 V
[Icw] rated short-time withstand current
5.5 kA - 10 s<br />4.6 kA - 30 s<br />3.6 kA - 1 min<br />2.6 kA - 3 min<br />1.7 kA - 10 min
Associated fuse rating
800 A aM at <= 440 V for motor<br />630 A aM at <= 690 V for motor<br />1250 A gG at <= 690 V
Average impedance
0.000065 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
70 W AC-1 - Ith 1050 A<br />42 W AC-3 - Ith 800 A
compatibility code
LC1G
Pole contact composition
4 NO
Auxiliary contact composition
1 NO + 1 NC
Irms rated making capacity
7640 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Safety reliability level
B10d = 100000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 1800000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
5 Mcycles
inrush power in VA (50/60 Hz, AC)
670 VA
inrush power in W (DC)
390 W
hold-in power consumption in VA (50/60 Hz, AC)
17.0 VA
hold-in power consumption in W (DC)
11.0 W
Operating time
40...70 ms closing<br />15...50 ms opening
Maximum operating rate
600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1
Connections - terminals
Power circuit: bar 2 - busbar cross section: 52 x 20 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit: bolted connection<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end
Connection pitch
2.8 in (70 mm)
Mounting Support
Plate
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />UL 60335-1<br />UL 60335-2-40:Annex JJ
Product Certifications
CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL
Tightening torque
513.3 lbf.in (58 N.m)
Height
15.3 in (388.5 mm)
Width
11.06 in (281 mm)
Depth
10.5 in (266 mm)
Net Weight
48.5 lb(US) (22 kg)
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation
-13…140 °F (-25…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Mechanical robustness
Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed
color
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C) at Uc

Specifications may be subject to change without notice