schneider XB5FVM5C1

Selling Points

  • 1High-capacity power distribution for large-scale applications.
  • 2Advanced thermal management for extended lifespan.
  • 3Compact design with enhanced portability options.
  • 4Integrated safety features including overcurrent protection.
  • 5Compatible with a wide range of electrical systems.
Product Details
XB5FVM5C1
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony XB5
Product or Component Type
Pilot light
Device short name
XB5F
Bezel material
Plastic colour plated white
Fixing collar material
Plastic
Head type
Built-in-flush
Mounting diameter
1.2 in (30.5 mm)
Sale per indivisible quantity
1
Shape of signaling unit head
Round
cap/operator or lens colour
Orange
Operator additional information
With plain lens
Light source
Protected LED
Bulb base
Integral LED
Light source colour
Orange
[Us] rated supply voltage
230...240 V AC 50/60 Hz
Device presentation
Complete product
Height
1.7 in (42 mm)
Width
1.4 in (36.6 mm)
Depth
2.2 in (55 mm)
Terminals description ISO n°1
(X1-X2)PL
Net Weight
0.084 lb(US) (0.038 kg)
Resistance to high pressure washer
1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end EN/IEC 60947-1<br />Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end EN/IEC 60947-1
[Ui] rated insulation voltage
250 V 3)EN 60947-1
[Uimp] rated impulse withstand voltage
4 kV EN 60947-1
Signalling type
Steady
GCR BRIDGE
XB5FVCUST05
Supply voltage limits
195…264 V AC
current consumption
14 mA
Service life
100000 h at rated voltage and 25 °C
Surge withstand
1 kV IEC 61000-4-5
Protective treatment
TH
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient Air Temperature for Operation
-40…158 °F (-40…70 °C)
Overvoltage category
Class II IEC 60536
IP degree of protection
IP66 IEC 60529<br />IP67 IEC 60529
NEMA degree of protection
NEMA 13<br />NEMA 4X
IK degree of protection
IK03 conforming to IEC 50102
Product Certifications
UL Listed<br />CSA
Vibration resistance
5 gn 12…500 Hz)IEC 60068-2-6
Shock resistance
50 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />30 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Resistance to fast transients
2 kV IEC 61000-4-4
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3
Electromagnetic compatibility
Electrostatic discharge - test level: 6 kV (on contact (on metal parts)) conforming to IEC 61000-4-2<br />Electrostatic discharge - test level: 8 kV (in free air (in insulating parts)) conforming to IEC 61000-4-2<br />Electromagnetic emission class B conforming to IEC 55011
Resistance to electrostatic discharge
6 kV on contact (on metal parts) IEC 61000-4-2<br />8 kV in free air (in insulating parts) IEC 61000-4-2
Electromagnetic emission
Class B IEC 55011

Specifications may be subject to change without notice