schneider XB7EA21P

Selling Points

  • 1Designed for 1 million cycles of slow-break operation.
  • 2Mounting diameter of 22 mm, ideal for space-efficient installations.
  • 3IP20 on the rear face and IP54 on the front face for robust protection.
  • 4Fixing nut beneath head with recommended torque of 2.2 N.m.
  • 5Compatible with various screwdrivers (JIS No 1, Philips No 1, pozidriv No 1) and flat screwdrivers (Ø 4 mm and Ø 5.5 mm).
Product Details
XB7EA21P
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony XB7
Product or Component Type
Push-button
Device short name
XB7
Mounting diameter
0.9 in (22 mm)
Sale per indivisible quantity
10
IP degree of protection
IP20 IEC 60529 rear face)<br />IP54 IEC 60529 front face)
Shape of signaling unit head
Round
Type of operator
spring return
Operator profile
Black flush, unmarked
Contacts type and composition
1 NO
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end EN/IEC 60947-1<br />Screw clamp terminals, 1 x 0.34...2 x 2.5 mm² without cable end EN/IEC 60947-1
Device presentation
Monolithic product
CAD overall width
1.1 in (29 mm)
CAD overall height
1.1 in (29 mm)
CAD overall depth
2.05 in (52 mm)
Terminals description ISO n°1
(13-14)NO
Net Weight
0.04 lb(US) (0.02 kg)
Device mounting
Fixing hole 0.9 in (22.5 mm) 22.3 +0.4/0 EN/IEC 60947-1
Fixing center
>= 30 x 40 mm support panel) metal 0.04…0.2 in (1…6 mm)<br />>= 30 x 40 mm support panel) plastic 0.08…0.2 in (2…6 mm)
Fixing mode
Fixing nut beneath head 17.7…21.2 lbf.in (2…2.4 N.m)
Contact operation
Slow-break
Positive opening
Without
Mechanical durability
1000000 cycles
Tightening torque
7.08…10.6 lbf.in (0.8…1.2 N.m) EN 60947-1
Shape of screw head
Cross JIS No 1<br />Cross Philips no 1<br />Cross pozidriv No 1<br />Slotted flat Ø 4 mm<br />Slotted flat Ø 5.5 mm
Short-circuit protection
4 A cartridge fuse gG EN/IEC 60947-5-1
[Ui] rated insulation voltage
250 V 3)EN/IEC 60947-1
[Uimp] rated impulse withstand voltage
4 kV EN/IEC 60947-1
[Ie] rated operational current
0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1<br />0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1<br />0.3 A 240 V, AC-14, D300 EN/IEC 60947-5-1<br />0.6 A 120 V, AC-14, D300 EN/IEC 60947-5-1
Electrical durability
1000000 cycles, DC-13, 0.3 A 24 V 216000 cyc/mn 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 0.03 A 230 V 216000 cyc/mn 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 0.09 A 240 V 108000 cyc/mn 0.5 EN/IEC 60947-5-1 appendix C
Electrical reliability
Λ <= 10exp(-6) 17 V, 5 mA EN/IEC 60947-5-4
Protective treatment
TH
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient Air Temperature for Operation
-13…158 °F (-25…70 °C)
Overvoltage category
Class II IEC 60536
NEMA degree of protection
NEMA 12
Standards
EN/IEC 60947-5-1<br />JIS C8201-5-1<br />UL 508<br />CSA C22.2 No 14<br />EN/IEC 60947-1<br />JIS C8201-1
Vibration resistance
5 gn 2…500 Hz)IEC 60068-2-6
Shock resistance
50 gn 11 ms) half sine wave acceleration IEC 60068-2-27

Specifications may be subject to change without notice