Product Model
3VA2116-6JP42-0AA0

Selling Points
- 1High breaking capacity up to 85 kA at 415 V.
- 2Selective protection response in rated operational current interval.
- 3Integrated metering function for energy data collection.
- 4Compact dimensions with fixed-mounting, plug-in, and draw-out technology.
- 5Modular and easy-to-fit internal accessories for diverse functions.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Breaking Capacity Ics(kA):@400V or 415V | 85 | Rated Voltage(V): | 690 |
Number of Poles: | 4P | Description | 3VA2H160 R160 ETU550 F/4P; 3VA2_160 dimensions; Rated current 160A; Interrupting rating H:85kA; Trip unit ETU550; |
Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, reset and select trip unit first) | ETU550【Electronic LSI+LCD】 |
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 85 | Interrupting Rating: | H:85kA |
Rated Current In(A): | 160 | Specifications: | 160【1-160A】 |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | 9N9999 | AL | N |
Model Number | 3VA2116-6JP42-0AA0 |