Product Model
3VA2216-5MQ32-0AA0

Selling Points
- 1High breaking capacity of 55 kA at 415 V for efficient short-circuit protection.
- 2Integrated motor protection with ETU860M for enhanced reliability.
- 3Advanced communication capabilities via various bus systems for seamless integration.
- 4Compact design with 3-pole configuration, ideal for industrial applications.
- 5Overload protection up to 160 A with precise current measurement for optimal system monitoring.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Intermittent Breaking Capacity Ics(kA):@400V or 415V | 55 | Rated Voltage(V): | 690 |
Number of Poles: | 3P | Description | 3VA2M250 R160 ETU860M F/3P; 3VA2_250 dimensions; Rated Current 160A; Interrupting Rating M:55kA; Trip Unit ETU860M; |
Mounting Method: | F: Fixed Type | Trip Unit: (If required is not in the list, click reset, select trip unit first) | ETU860M【Motor Protection, LSIG+LCD+Mea】 |
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 55 | Interrupting Rating: | M:55kA |
Rated Current In(A): | 160 | Specifications: | 250【160-250A】 |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | 9N9999 | AL | N |
Model Number | 3VA2216-5MQ32-0AA0 |
Specifications may be subject to change without notice