Product Model
3VA2450-7MQ32-0AA0

Selling Points
- 1High Breaking Capacity: 110 kA at 415 V, ensuring reliable short-circuit protection.
- 2Motor Protection: Equipped with ETU860M and LSIG for comprehensive motor protection.
- 3Adjustable Parameters: Customizable response values for tailored protection settings.
- 4Durable Design: Mechanical service life of 15,000 switching cycles, withstanding harsh operating conditions.
- 5Enhanced Safety Features: Ground fault protection with I2t characteristic, ensuring secure operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Intermittent Breaking Capacity Ics(kA):@400V or 415V | 110 | Rated Voltage(V): | 690 |
Number of Poles: | 3P | Description | 3VA2C630 R500 ETU860M F/3P; 3VA2_630 Dimensions; Rated Current 500A; Interrupting C:110kA; Trip Unit ETU860M; |
Mounting Method: | F: Fixed Type | Trip Unit: (If required is not in the list, reset and select trip unit first) | ETU860M【Motor Protection, LSIG+LCD+Mea】 |
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 110 | Interrupting Rating: | C:110kA |
Rated Current In(A): | 500 | Specifications: | 630【400-630A】 |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | 9N9999 | AL | N |
Model Number | 3VA2450-7MQ32-0AA0 |
Specifications may be subject to change without notice