Product Model
3VM1125-3GD42-0AA0

Selling Points
- 1Robust Short-Circuit Protection: Designed to handle up to 25 kA at 415 V, ensuring reliable operation under high short-circuit conditions.
- 2Advanced Overload Protection: Equipped with fixed overload protection (Ir) and instantaneous short-circuit protection (Ii), providing comprehensive safety.
- 3Compact and Modular Design: Compact dimensions (70 mm depth, 101.6 mm width) and modular accessories for easy installation and customization.
- 4High Insulation Voltage: Rated insulation voltage of 690 V, ensuring reliable operation in various electrical environments.
- 5Durable Construction: Built to last with a mechanical service life of 20,000 operating cycles and electrical endurance up to 9,000 cycles at 380/415 V AC.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Breaking Capacity Ics(kA): @400V or 415V | 18 | Rated Voltage(V): | 415 |
Number of Poles: | 4P | Description | 3VM1N160 R25 TM210N F/4P; Size 160; Rated Current 25A; Interrupting N: 25kA; Trip Unit TM210N; |
Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM210N [LI fixed, with N-phase protection] |
Rated Ultimate Breaking Capacity Icu(kA): @400V or 415V | 25 | Interrupting Rating: | N: 25kA |
Rated Current In(A): | 25 | Specifications: | 160 [8-160A] |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | N | AL | N |
Model Number | 3VM1125-3GD42-0AA0 |