Product Model
3VM1163-5ED42-0AA0

Selling Points
- 1The 3VM1163-5ED42-0AA0 circuit breaker features a breaking capacity of up to 55 kA at 415 V, ensuring reliable line protection.
- 2Designed with modularity in mind, this circuit breaker allows for easy installation and quick replacement of accessories.
- 3With a mounting depth of 70 mm and a cover size of 45 mm, it is ideal for protecting cables and lines in plant areas.
- 4Equipped with a thermal-magnetic trip unit for providing overload and short-circuit protection in AC/DC applications.
- 5Meets IEC/EN 60947-1, IEC/EN 60947-2, and other relevant standards for electromagnetic compatibility and safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Breaking Capacity Ics(kA): @400V or 415V | 41 | Rated Voltage(V): | 415 |
Number of Poles: | 4P | Description | 3VM1M160 R63 TM210 F/4P; Size 160; Rated Current 63A; Interrupting Rating M: 55kA; Trip Unit TM210; |
Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, click reset, then select the trip unit) | TM210 [LI fixed, line protection] |
Rated Ultimate Breaking Capacity Icu(kA): @400V or 415V | 55 | Interrupting Rating: | M: 55kA |
Rated Current In(A): | 63 | Specifications: | 160 [8-160A] |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | N | AL | N |
Model Number | 3VM1163-5ED42-0AA0 |
Specifications may be subject to change without notice