Product Model

3WT8081-8UG04-5AB1

In Stock
Last updated: 2025/4/28
Siemens 3WT8081-8UG04-5AB1

Selling Points

  • 1High breaking capacity up to 66 kA at 500V/690V.
  • 2Advanced protection functions including overload, short-time delay short-circuit, and ground-fault tripping.
  • 3Modular design with electronic trip units (ETU) for customizable protection.
  • 4User-friendly interface with clear indicators for easy operation.
  • 5Compliance with international standards for safety and reliability.
Product Details
3WT8081-8UG04-5AB1
Siemens

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Rated Voltage (V)
500
Description
3WT1, 800A ETU47WT D/3P, 66kA; Electric Operation for Closing AC/DC220V; Shunt Trip AC/DC220V; Alarm Contacts; Safety Shield; Door Frame; 2NO+2NC
Icw(kA)
50
Rated Operating Short-circuit Breaking Capacity Ics(kA)@400V or 415V
66
Control Voltage
AC/DC220V
Number of Poles
3P
Installation Method
D: Drawer Type
Trip Unit
ETU47WT【LSING With LCD Display】
Rated Current In(A)
800
Rated Ultimate Breaking Capacity Icu(kA)@400V or 415V
66
Breaking Capacity Level
S:66kA
Specifications
3WT1【400-1600A】
Lifecycle
Delivery Release (PM300)
Country of Origin
China
ECCN
N
AL
N
Model Number
3WT8081-8UG04-5AB1

Specifications may be subject to change without notice