Product Model

2006-931/1000-541

In Stock
Last updated: 2025/4/30
wago 2006-931/1000-541

Selling Points

  • 1The WAGO Fuse Plug 2006-931/1000-541 ensures reliable and secure connections with its pull-tab design.
  • 2Compatible with glass cartridge fuses ¼" x 1¼", making it versatile for various applications.
  • 3Equipped with an indicator lamp for 12-30V, providing visual confirmation of fuse status.
  • 4Measuring 7.4 mm wide, this fuse plug is compact and space-efficient.
  • 5Available in gray, making it easy to identify and integrate into your electrical systems.
Product Details
2006-931/1000-541
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
7.4?mm?/ 0.291?inches
Marking level
Center marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.106MJ
Weight
6.8g
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-49
eCl@ss 9.0
27-14-11-49
ETIM 9.0
EC002018
ETIM 8.0
EC002018
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4045454820893
Customs tariff number
8536694040
CAS-No.
1303-86-2
REACH Candidate List Substance
Diboron trioxide
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
7(a)
SCIP notification number (Austria)
4cf79648-9093-43c0-8d3a-c1eed3452fa8
SCIP notification number (Belgium)
f764b39e-df6b-46d6-9927-42f8b254fc80
SCIP notification number (Bulgaria)
caf0a164-3c23-4511-bc42-7888aafe5121
SCIP notification number (Czech Republic)
9e06c12b-20e8-482d-99d7-8a0e2b9dd458
SCIP notification number (Denmark)
37c6b190-8246-44ee-b40d-0623b1022c20
SCIP notification number (Finland)
db8274fe-f1fd-4416-8654-24a1661f305d
SCIP notification number (France)
cf92069c-9006-453e-9293-d5c88aeae2f0
SCIP notification number (Germany)
cf6b413c-62ee-4f9d-a07a-8724277f68c6
SCIP notification number (Hungary)
0988d150-bc2e-41c0-9d55-028a5e8d391a
SCIP notification number (Italy)
82723aba-685d-4e44-9c66-655de63fb131
SCIP notification number (Netherlands)
25b4315a-509a-4e91-8eaf-d6a89a740be6
SCIP notification number (Poland)
bcf2431d-6d6d-4437-bd6a-133241e6cbba
SCIP notification number (Romania)
d2d002aa-9e0d-4af8-ba78-aa73ffb7cfdf
SCIP notification number (Sweden)
0f5bc62a-d7ae-42f2-ac76-3c17af74e6c6
Rated voltage (III / 3)
800V
Rated current
10A
Operation status indicator
12 … 30?V
Blown fuse indication
with indicator lamp
Ratings (note)
Electrical ratings are given by the fuse and blown fuse indication.
Rated current (note)
Leakage current in case of a blown fuse: LED 2 mA
Ratings per 2
IEC/EN 60947-7-3
Rated voltage (III/3) 2
30V
Rated surge voltage (III/3) 2
0.8kV
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
30V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
30V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
15A
Power loss (max.) P<sub>l (max.)</sub> (note)
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN?60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Fuse type
Cylindrical fuse; ?" x 1?"
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice