Product Model
2202-1311/1000-411

Selling Points
- 1Made from high-quality polyamide (PA66) for excellent insulation and durability.
- 2Features push-in CAGE CLAMP technology for quick and tool-free conductor connection.
- 3Designed for DIN-rail 35 x 15 and 35 x 7.5, ensuring versatile mounting options.
- 4Rated for 0.5 A, making it suitable for various electrical applications.
- 5Equipped with a 1N4007 diode for reliable protection against voltage spikes.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 3 | Total number of potentials | 1 |
Number of levels | 1 | Number of jumper slots | 1 |
Width | 5.2 mm / 0.205 inches | Height | 59.2 mm / 2.33 inches |
Depth from upper-edge of DIN-rail | 32.9 mm / 1.295 inches | Mounting type | DIN-35 rail |
Marking level | Center/side marking | Note (material data) | Information on material specifications can be found here |
Color | gray | Material group | I |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire load | 0.175MJ | Weight | 7.9g |
Processing temperature | -35 … +85 °C | Continuous operating temperature | -60 … +105 °C |
ECCN | NO US CLASSIFICATION | PU (SPU) | 100?pcs |
Packaging type | Box | Country of origin | DE |
GTIN | 4066966324365 | Customs tariff number | 85369010000 |
CAS-No. | 7439-92-1 | REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol |
RoHS Compliance Status | Compliant,With Exemption | RoHS Exemption | 7(a) |
SCIP notification number (Austria) | 52bbdf8d-491c-4335-ae66-9a23dfc3b192 | SCIP notification number (Belgium) | 41f43c12-bc9d-4814-8b81-b0fb62340ea7 |
SCIP notification number (Czech Republic) | 0954dac7-24c1-47b5-992b-1903155d731d | SCIP notification number (Denmark) | 26658a57-77eb-491c-9c77-e40f1a1d5f43 |
SCIP notification number (Finland) | dc9a1531-9b18-4304-8792-d807115d4b25 | SCIP notification number (Germany) | 7a0f3cab-2fb2-4ca5-8691-b648ac46ecb5 |
SCIP notification number (Netherlands) | 63f2ed46-ac92-44b5-bf92-74a85b7f9a71 | SCIP notification number (Poland) | 8b297668-adcc-435a-9d8a-1ca2e0e888bf |
SCIP notification number (Romania) | ffd462ca-0a4f-4b69-87b9-002ccc007df6 | SCIP notification number (Sweden) | f061c383-1f07-4926-8233-f2b07e3a1844 |
Nominal voltage | 250V | Reverse voltage | 1,000V |
Continuous current (max.) | 500 mA | Connection technology | Push-in CAGE CLAMP? |
Actuation type | Push-button | Connectable conductor materials | Copper |
Nominal cross-section | 2.5 mm2 | Solid conductor | 0.25 … 4 mm2 / 22 … 12 AWG |
Solid conductor; push-in termination | 0.75 … 4 mm2 / 18 … 12 AWG | Fine-stranded conductor | 0.25 … 4 mm2 / 22 … 12 AWG |
Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5 mm2 / 22 … 14 AWG | Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5 mm2 / 18 … 14 AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. | Strip length | 10 … 12 mm / 0.39 … 0.47 inches |
Wiring direction | Front-entry wiring | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice