wago 264-112

Selling Points

  • 1Made from durable aluminum for long-lasting performance.
  • 2Ideal for various electrical applications with 24 connections and 12 potentials.
  • 3Secure and easy to use, ensuring reliable connections.
  • 4Durable gray finish for easy identification in complex electrical systems.
  • 5Supports high voltage applications with a rated voltage of 800V.
Product Details
264-112
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
24
Total number of potentials
12
Number of levels
1
Width
88?mm?/ 3.465?inches
Height from the surface
22.1?mm?/ 0.87?inches
Depth
32?mm?/ 1.26?inches
Module width
6?mm?/ 0.236?inches
Design
horizontal type
Mounting type
Mounting flange
Marking level
Center marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.961MJ
Halogen-free
Yes
Weight
49.8g
eCl@ss 10.0
27-14-11-06
eCl@ss 9.0
27-14-11-06
ETIM 9.0
EC001284
ETIM 8.0
EC001284
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4044918425919
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
24A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
20A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
20A
Connection technology
CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Solid conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Note (conductor cross-section)
12 AWG: THHN, THWN
Strip length
8 … 9?mm?/ 0.31 … 0.35?inches
Number of poles
12
Wiring direction
Front-entry wiring

Specifications may be subject to change without notice