Product Model
282-903

Selling Points
- 1Designed for DIN-rail mounting (35 x 15 and 35 x 7.5)
- 2CAGE CLAMP technology for secure connections
- 3Robust 6 mm² conductor capacity
- 4Center marking for easy identification
- 5Ideal for industrial applications requiring reliability
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 2 | Total number of potentials | 1 |
Number of levels | 1 | Width | 8?mm?/ 0.315?inches |
Height | 74.5?mm?/ 2.933?inches | Depth from upper-edge of DIN-rail | 32.5?mm?/ 1.28?inches |
Mounting type | DIN-35 rail | Marking level | Center marking |
Note (material data) | Information on material specifications can be found here | Color | red |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.267MJ |
Weight | 15.8g | Processing temperature | -35 … +85?°C |
Continuous operating temperature | -60 … +105?°C | ETIM 9.0 | EC000897 |
ETIM 8.0 | EC000897 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 50?pcs | Packaging type | Box |
Country of origin | PL | GTIN | 4066966232011 |
Customs tariff number | 85369010000 | RoHS Compliance Status | Compliant,No Exemption |
Ratings per | IEC/EN 60947-7-1 | Rated voltage (III / 3) | 800V |
Rated impulse voltage (III / 3) | 8kV | Rated current | 41A |
Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 | Power loss, per pole (potential) | 1.311W |
Rated current I<sub>N</sub> for specified power loss | 41A | Resistance value for specified, current-dependent power loss | 0.001Ω |
Connection technology | CAGE CLAMP? | Actuation type | Operating tool |
Connectable conductor materials | Copper | Solid conductor | 0.2 … 6?mm2?/ 24 … 10?AWG |
Fine-stranded conductor | 0.2 … 6?mm2?/ 24 … 10?AWG | Strip length | 12 … 13?mm?/ 0.47 … 0.51?inches |
Wiring direction | Front-entry wiring |
Specifications may be subject to change without notice