wago 284-902

Selling Points

  • 1High-Current Capability: Withstands up to 22,200 A for 1 second without damage.
  • 2Automatic Clamping: CAGE CLAMP technology ensures secure connections without wire damage.
  • 3Compact Design: Ideal for rail-mounted applications with a small footprint.
  • 4Versatile Conductor Range: Supports conductors from 0.14 to 1.5 mm².
  • 5Durable Construction: Made from high-quality materials for long-lasting performance.
Product Details
284-902
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Width
10?mm?/ 0.394?inches
Height
78?mm?/ 3.071?inches
Depth from upper-edge of DIN-rail
35?mm?/ 1.378?inches
Mounting type
DIN-35 rail
Marking level
Center marking
Note (material data)
Information on material specifications can be found here
Color
orange
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.348MJ
Weight
23.2g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
1 (Rail Mounted Terminal Blocks)
eCl@ss 10.0
27-14-11-20
eCl@ss 9.0
27-14-11-20
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4044918305754
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60947-7-1
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
57A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Power loss, per pole (potential)
1.819W
Rated current I<sub>N</sub> for specified power loss
57A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Solid conductor
0.2 … 10?mm2?/ 24 … 8?AWG
Fine-stranded conductor
0.2 … 10?mm2?/ 24 … 8?AWG
Strip length
12 … 13?mm?/ 0.47 … 0.51?inches
Wiring direction
Front-entry wiring

Specifications may be subject to change without notice