Product Model

288-304

In Stock
Last updated: 2025/4/29
wago 288-304

Selling Points

  • 1General-purpose SPDT (1 Form C) relay with 24VDC coil.
  • 2DIN rail mounting for easy installation.
  • 3Limiting continuous current of 6 A.
  • 4Compact module width of 21 mm.
  • 5Pre-soldered relay with 1 changeover contact.
Product Details
288-304
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Note
Reinforced insulation between control and load side per EN 61010-2-201
Rated voltage
300V
Overvoltage category
II
Pollution degree
2
Dielectric strength (control/load circuit) (AC, 1?min)
4?kVrms
Dielectric strength (open contact) (AC, 1?min)
1?kVrms
Connection technology
CAGE CLAMP?
WAGO connector
WAGO 236 Series
Solid conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Strip length
5 … 6?mm?/ 0.2 … 0.24?inches
Width
20.5?mm?/ 0.807?inches
Height
85?mm?/ 3.346?inches
Depth from upper-edge of DIN-rail
48?mm?/ 1.89?inches
Mounting type
DIN-35 rail
Note (material data)
Information on material specifications can be found here
Color
gray
Fire load
1.033MJ
Weight
45g
Ambient temperature (operation at U<sub>N</sub>)
-25 … +40 °C
Ambient temperature (storage)
-40 … +80 °C
Processing temperature
-25 … +50?°C
Relative humidity
5 … 75?% (non-condensing)
Standards/specifications
EN 61010-2-201
Product Group
6 (INTERFACE ELECTRONIC)
eCl@ss 10.0
27-37-16-01
eCl@ss 9.0
27-37-16-01
ETIM 9.0
EC001437
ETIM 8.0
EC001437
ECCN
NO US CLASSIFICATION
PU (SPU)
10?(1)?pcs
Packaging type
box
Country of origin
CN
GTIN
4045454468033
Customs tariff number
8536490050
CAS-No.
7439-92-1
REACH Candidate List Substance
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
7(a)
SCIP notification number (Austria)
d018b739-53e8-42b3-87a2-624542f953d5
SCIP notification number (Belgium)
3cfb7a70-68a9-4954-9c89-c2fe289a4d6f
SCIP notification number (Bulgaria)
0e164143-232e-4d5b-8e7c-66b01c11fdbf
SCIP notification number (Czech Republic)
ab74f637-d1e0-4a5b-99fc-7b381dc6339c
SCIP notification number (Denmark)
5225a512-d643-4bfc-ad4b-535499d9a3cf
SCIP notification number (Finland)
2e9aedd1-9120-49ae-9134-93cf46c97b9f
SCIP notification number (France)
ef7bc1ed-834d-4324-b243-137318355e68
SCIP notification number (Germany)
7c9b0dd4-3a93-43ad-98f7-c1005df99464
SCIP notification number (Hungary)
e4938b9a-32d8-4d2a-8cf1-a0f92746e456
SCIP notification number (Italy)
bd03d75b-7bc1-4273-9c9e-dd6c34008bf1
SCIP notification number (Netherlands)
08d33b71-aa54-42a4-bf52-5db20297cb7c
SCIP notification number (Poland)
7a4a0269-0fd0-4d3f-975f-991fef56aaa1
SCIP notification number (Romania)
eaa7f9a2-b6ad-4c58-bef8-6e90ad97aff9
SCIP notification number (Sweden)
793b3109-62da-4977-be57-ab4c86f50829
Nominal input voltage U<sub>N</sub>
DC?24?V
Input voltage range
±10?%
Nominal input current at U<sub>N</sub>
22?mA
Number of changeover contacts
1
Contact material (relay)
AgNi 90/10
Limiting continuous current
6?A
Inrush current (resistive) max.
(AC) 16?A?/ 4?s
Switching Voltage, Max.
AC?250?V
Switching power (resistive) max.
AC?1500?VA
Pull-in time (typ.)
9ms
Drop-out time (typ.)
3ms
Bounce time (typ.)
2ms
Electrical life (NO; resistive load; 23?°C)
100?x 103 switching operations
Mechanical life
30?x 10? switching operations