Product Model

787-1012

In Stock
Last updated: 2025/6/16
wago 787-1012

Selling Points

  • 1High Load-Carrying Capacity: Handles high capacitive loads and maintains constant current under overload conditions.
  • 2Versatile Mounting Options: Can be mounted on DIN-rails, screw-mount clips, or wall-mount adapters for flexible installation.
  • 3Slim Design: Reduces cabinet space by up to 45% compared to previous models, ideal for compact installations.
  • 4Clear Indication: Features LEDs for clear status indication, including green (DC OK), yellow (warning), and red (fault or overload).
  • 5High Operational Reliability: Operates efficiently on a wide input voltage range (85–264 VAC) and withstands voltage fluctuations within a power grid.
Product Details
787-1012
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Protection class
II
Protection type
IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
≤ 40 VDC (in the event of a fault)
Short-circuit-protected
Yes
Open-circuit-proof
Yes
Parallel operation
Yes
Series operation
Yes
MTBF
> 500,000 h (per IEC 61709)
Connection type 1
Input/Output
Connection technology
CAGE CLAMP?
WAGO connector
WAGO 740 Series
Solid conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Strip length
6 … 7?mm?/ 0.24 … 0.28?inches
Width
72?mm?/ 2.835?inches
Height
89?mm?/ 3.504?inches
Depth
59?mm?/ 2.323?inches
Depth from upper-edge of DIN-rail
55?mm?/ 2.165?inches
Housing design
DIN-rail-mount enclosure
Mounting type
DIN-35 rail
Flammability class per UL94
V0
Weight
10.9g
Ambient temperature (operation)
-25 … +60 °C (Device starts at ?40 °C (type-tested))
Ambient temperature (storage)
-25 … +80 °C
Ambient temperature UL (operation at U<sub>N</sub>)
-25 … +55 °C
Relative humidity
5 … 96?% (no condensation permissible)
Derating
?3 %/K (> 45 °C)
Climatic category
3K3 (per EN 60721)
Conformity marking
CE
Standards/specifications
EN 61010-1
Product Group
6 (INTERFACE ELECTRONIC)
eCl@ss 10.0
27-04-07-01
eCl@ss 9.0
27-04-07-01
ETIM 9.0
EC002540
ETIM 8.0
EC002540
ECCN
NO US CLASSIFICATION
PU (SPU)
1?pcs
Packaging type
box
Country of origin
CN
GTIN
4050821297598
Customs tariff number
8504409510
RoHS Compliance Status
Compliant,No Exemption
Phases
1
Nominal input voltage [V]
1 x AC?100 … 240?V
Input voltage range
1 x AC?85 … 264?V;?DC?120 … 300?V
Input voltage derating
Io≤ 2 A (< 100 VAC); Io≤ 1.8 A (< 90 VAC)
Nominal mains frequency range
44 … 66 Hz;0 Hz
Input current I<sub>i</sub>
≤?0.6?A (230?VAC);?≤?1.4?A (110?VAC)
Inrush current
≤?30?A (NTC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥?80?ms (230?VAC);?≥?10?ms (110 VAC)
Nominal output voltage [V]
DC?24?V (SELV)
Output voltage range
DC?24?V
Default setting
DC?24?V
Nominal output current I<sub>o nom</sub>
2.5?A (24?VDC);?1.6?A (in any mounting position)
Nominal output power
60W
Deviation
≤?2?%
Residual ripple
≤?100?mV (peak-to-peak)
Current limitation
1.1 x Io nom(typ.)
Overload behavior
Constant current
Signaling
1 x Status indication LED (green)
Operation status indicator
Green LED (Uo)
Power loss P<sub>l</sub>
≤?2.2?W;?≤?8.5?W (230 VAC; nominal load)
Power loss (max.) P<sub>l (max.)</sub>
10.5?W (100 VAC / 24 VDC; 2.5 A)
Efficiency (typ.)
88?%
Internal fuse
T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6?A (C characteristic), 10 A (B characteristic) or higher

Specifications may be subject to change without notice