Product Model

826-160/000-016

In Stock
Last updated: 2025/4/28
wago 826-160/000-016

Selling Points

  • 1Secure Wiring: Utilizes CAGE CLAMP spring connections for secure and easy wiring.
  • 2Tool-Free Installation: Easy, tool-free installation ensures quick setup.
  • 3Direct Ground Contact: Provides direct ground contact with enclosure/panel for reliable electrical connections.
  • 4Compliant Standards: Meets UL 1059 and IEC/EN 60664-1 standards for safety and performance.
  • 5Versatile Design: Compatible with plate thicknesses from 1 to 4 mm and supports up to 32A rated current.
Product Details
826-160/000-016
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Variants:
Other pole numbers
Clamping units
2
Total number of potentials
1
Number of connection types
2
Number of levels
1
Pin spacing
7?mm?/ 0.276?inches
Width
7?mm?/ 0.276?inches
Height
23.55?mm?/ 0.927?inches
Depth
42.5?mm?/ 1.673?inches
Housing sheet thickness
1 … 4?mm?/ 0.039 … 0.157?inches
Mounting type
Feed-through mounting
Note (material data)
Information on material specifications can be found here
Color
green-yellow
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Tin
Fire load
0.08MJ
Weight
5.4g
Limit temperature range
-60 … +105?°C
Processing temperature
-35 … +60?°C
eCl@ss 10.0
27-14-11-06
eCl@ss 9.0
27-14-11-06
ETIM 9.0
EC001284
ETIM 8.0
EC001284
ECCN
NO US CLASSIFICATION
PU (SPU)
50?(25)?pcs
Packaging type
box
Country of origin
DE
GTIN
4044918546843
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60664-1
Rated voltage (III / 3)
320V
Rated impulse voltage (III / 3)
4kV
Rated voltage (III/2)
320V
Rated surge voltage (III/2)
4kV
Nominal voltage (II/2)
630V
Rated surge voltage (II/2)
4kV
Rated current
32A
Legend (ratings)
(III / 2) ? Overvoltage category III / Pollution degree 2
Ratings (note)
Suitable for neutral-grounded, three-phase, 4-wire systems rated at 400 V (conductor-to-conductor) per IEC/EN 60664-1.
Approvals per
CSA
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group C)
150V
Rated current UL (Use Group C)
20A
Rated voltage UL (Use Group D)
300V
Rated current UL (Use Group D)
10A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
20A
Rated voltage CSA (Use Group C)
150V
Rated current CSA (Use Group C)
20A
Rated voltage CSA (Use Group D)
300V
Rated current CSA (Use Group D)
10A
Connection technology
CAGE CLAMP?
Actuation type
Operating tool
Solid conductor
0.08 … 4?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 4?mm2?/ 28 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2
Fine-stranded conductor; with uninsulated ferrule
0.25 … 2.5?mm2
Strip length
9 … 10?mm?/ 0.35 … 0.39?inches
Number of poles
1