wago 885-310

Selling Points

  • 1High-Current Capability: Supports up to 269A rated current for demanding electrical applications.
  • 2DIN-Rail Mounting: Easily mounts on DIN-rail 35 x 15 or 35 x 7.5, ensuring versatile installation options.
  • 3Robust Construction: Made from durable gray material with a fire load of 0.831 MJ, ensuring long-lasting performance.
  • 4Screw-Clamp Connection: Features screw-clamp connection technology with M10 stud bolts for secure conductor connections.
  • 5Comprehensive Certifications: Meets overvoltage category III and pollution degree 3 standards, certified by DEKRA and UL.
Product Details
885-310
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Width
33.8?mm?/ 1.331?inches
Height
67?mm?/ 2.638?inches
Depth from upper-edge of DIN-rail
66.7?mm?/ 2.626?inches
Tightening torque
10 … 20?Nm
Mounting type
DIN-35 rail
Marking level
Side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.831MJ
Weight
228.2g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
1 (Rail Mounted Terminal Blocks)
eCl@ss 10.0
27-14-11-20
eCl@ss 9.0
27-14-11-20
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
10?pcs
Packaging type
box
Country of origin
CN
GTIN
4050821049272
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Rated voltage (III / 3)
1000V
Rated impulse voltage (III / 3)
8kV
Rated current
269A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Power loss, per pole (potential)
8.683W
Rated current I<sub>N</sub> for specified power loss
269A
Resistance value for specified, current-dependent power loss
Connection technology
Bolt-type connection
Actuation type
Open-end, ring, socket wrench; 17 mm
Connectable conductor materials
Copper
Clamping range
6 … 120?mm2?/ 10?AWG … 250?kcmil
Type of cable lugs per DIN 46234
Cable lugs for solder-free connectionsRing type, without insulating sleeve, for copper conductors
Type of cable lugs per DIN 46235
Cable lugs for compression connectionsCover plate type for copper conductors
Thread size
M10
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice